ABB i-Bus® EIB/KNX ABB Powernet EIB/KNX

ABB i-Bus® EIB/KNX ABB Powernet EIB/KNX

ABB i-Bus® EIB/KNX ABB Powernet EIB/KNX

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>ABB</strong> i-bus ® <strong>EIB</strong>/<strong>KNX</strong><br />

<strong>ABB</strong> <strong>Powernet</strong> <strong>EIB</strong>/<strong>KNX</strong><br />

LEANtouch (monochrome),<br />

SMARTtouch (monochrome, colour)<br />

Type: 6x36/30M…, 6x36/100x…, 6x36/100CB…<br />

Parameters: Room thermostat<br />

The default setting for the values<br />

is printed in bold type.<br />

Only for cooling:<br />

Setpoints cooling:<br />

– Dead zone between heating and 1…4…8<br />

cooling in K (1…8)<br />

– Increasing standby operation cooling 1…2…8<br />

– Increasing night operation cooling 1…4…8<br />

– Setpoint heat protection Cooling switched off<br />

30°C<br />

35°C<br />

40°C<br />

44°C<br />

Controlling/Control value cooling:<br />

– Output of control value continuously<br />

switched<br />

– Control type Two-position controller<br />

PI controller<br />

Only for two-position controller:<br />

– Hysteresis 0.3K / 0.5K / 0.7K / 1.0K / 1.5K / 2.0K<br />

– Lowering of hysteresis Inactive<br />

0.2 K/min<br />

0.1 K/min<br />

0.06 K/min<br />

0.04 K/min<br />

0.03 K/min<br />

0.02 K/min<br />

– Cycle time of the control value in 04:46<br />

mm:ss (03:00…60:00)<br />

– Effective mode Normal<br />

Inverted<br />

Only for PI controller:<br />

– Control parameters via installation type<br />

free setting of parameters<br />

– Type of cooling system Cooling ceiling (5K/240min)<br />

SplitUnit/Fan cooling (4K/90min)<br />

– PWM cycle 3min / 5min / 10min / 15min / 20min /<br />

30min / 40min / 50min / 60min<br />

– PWM cycle is 0% up to control value 0% / 10% / 20% / 30%<br />

– PWM cycle is 100% up to control value 70% / 80% / 90% / 100%<br />

– Effective mode Normal<br />

Inverted<br />

Only for free parameterisation:<br />

– Proportional area 1.0K / 1.5K / 2.0K / 2.5K / 3K / 4K /<br />

6K / 8K / 10K<br />

– Restet time in min. I part inactive / 10 min / 20 min / …<br />

100 min / … / 200 min / 240 min<br />

Only for continuous controller:<br />

– Cycle time of the control value in mm:ss 04:46<br />

(03:00…60:00)<br />

– Effective mode Normal<br />

Inverted<br />

– Change for automatic sending of Inactive / 2% / 5% / 10%<br />

control value<br />

May 2006 71