<strong>ABB</strong> i-bus ® <strong>EIB</strong>/<strong>KNX</strong><br />

<strong>ABB</strong> <strong>Powernet</strong> <strong>EIB</strong>/<strong>KNX</strong><br />

LEANtouch (monochrome),<br />

SMARTtouch (monochrome, colour)<br />

Type: 6x36/30M…, 6x36/100x…, 6x36/100CB…<br />

Parameters: Room thermostat<br />

The default setting for the values<br />

is printed in bold type.<br />

General:<br />

– Control heating Active<br />

– Control additional heating Inactive<br />

Active<br />

– Control cooling Inactive<br />

Active<br />

– Operation mode after reset Comfort<br />

Standby<br />

Night<br />

Frost protection<br />

– Cyclic sending of actual value and 14:50<br />

setpoint in mm.ss (03:00…60:00)<br />

– Change of actual temp. for Inactive / 0.2 K / 0.4 K / 0.6 K / 0.8 K /<br />

automatic sending<br />

1.0 K / 1.5 K / 2.0 K<br />

– Automatic shading (see also Inactive<br />

setpoints)<br />

Active<br />

– Party time (extension of comfort Inactive / 30 min / 1 h / 1.5 h / 2 h /<br />

mode)<br />

2.5 h / 3 h / 4 h<br />

– Display heating/cooling is active If operation mode is active<br />

At heating resp. cooling<br />

– Group master operation mode Inactive<br />

Active<br />

– Disable frost/heat protection manually Locked<br />

(extension of comfort mode)<br />

Free<br />

– Actual value survey Internal<br />

External<br />

– Toggle between heating and automatic<br />

cooling<br />

via object<br />

– Offset value in K x 0.1 K -127…0…+127<br />

Setpoints general:<br />

– Area for manual setpoint setting Disabled / +- 1K / +- 3K / +- 5K<br />

– Maximum increasing of setpoint 3<br />

at heating in K (0…5)<br />

Only for cooling:<br />

– Maximum lowering of setpoint 3<br />

at cooling in K (0…5)<br />

– Send actual setpoint at change Inactive<br />

Active<br />

– Manual setpoint setting Reset at receiving of base<br />

setpoint<br />

Hold at receiving of base<br />

setpoint<br />

Only for shading:<br />

– Shading setpoint Comfort temperature + 2K<br />

Comfort temperature + 4K<br />

Comfort temperature + 6K<br />

Comfort temperature + 8K<br />

– Temperature display at Act. setpoint<br />

setpoint adjustment<br />

Base setpoint<br />

May 2006 69