<strong>InduSoft</strong> <strong>Web</strong> <strong>Studio</strong><br />
Tutorial training – Revision B – Sep/10/2000<br />
© Copyright <strong>InduSoft</strong> Ltd. 2000<br />
If you type an Invalid Entry in these fields, they will accept it, but, when you try to close the<br />
Comm’s Parameter dialog, an error message will be shown, avoiding close the dialog.<br />
Advanced Settings<br />
By clicking in the button Advanced… in the windows Communication Parameters will be<br />
possible to configure other parameters of the serial communication:<br />
Parameter Default Value Valid values Description<br />
Start message (ms) 1000 0 to 10000<br />
Maximum time to receive<br />
the beginning of the<br />
answer from the device<br />
(time-out time)<br />
Maximum time to receive<br />
the end of the answer from<br />
the device since the<br />
End message (ms) 0 0 to 10000 beginning of the answer.<br />
(Note: the value zero mean<br />
that the driver won’t check<br />
these time)<br />
Interval between char 500 0 to 10000<br />
Maximum time between<br />
the characters sent from<br />
the device<br />
Wait CTS (ms) 100 0 to 10000<br />
Maximum time to receive<br />
the CTS signal after the set<br />
of the RTS signal (Note:<br />
valid only if the parameter<br />
Verify CTS has the value<br />
yes)<br />