Alternative Reader Wiring Guide - Best Access Systems
Alternative Reader Wiring Guide - Best Access Systems
Alternative Reader Wiring Guide - Best Access Systems
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Alternative</strong> <strong>Reader</strong> <strong>Wiring</strong> <strong>Guide</strong><br />
20.5. Indala <strong>Reader</strong>s ASR-500, ASR-501, ASR-503, ASR-505, ASR-110<br />
(Not evaluated by UL)<br />
20.5.1 <strong>Wiring</strong> the BAS-1300<br />
GND<br />
BZR<br />
LED<br />
CLK/D1<br />
Single <strong>Reader</strong><br />
Interface Module<br />
DAT/D0<br />
+12V<br />
Suggested<br />
Color Code<br />
(White)<br />
(Green)<br />
Splice Here<br />
Color<br />
Code<br />
<strong>Reader</strong> Cable<br />
(White)<br />
(Green)<br />
(Blue)<br />
(Brown)<br />
Do not use<br />
(Blue)<br />
(Orange)<br />
(Brown)<br />
(Black)<br />
ASR-500 <strong>Reader</strong>,<br />
ASR-501, ASR-503,<br />
ASR-505, ASR-110<br />
12 VDC<br />
Linear<br />
Power<br />
Supply<br />
-<br />
+<br />
(Black)<br />
(Red)<br />
(Red)<br />
Shield (Screen)<br />
EARTH GROUND<br />
revision 7 — 103