<strong>Alternative</strong> <strong>Reader</strong> <strong>Wiring</strong> <strong>Guide</strong><br />

19.2. Integrated Engineering PX007 Mifare <strong>Reader</strong><br />

The following information applies for these Integrated Engineering reader models: PX007Z/MFSNR,<br />

PX007MF/Read Only, and PX007MF/RS232(B).<br />

The reader operates between 4.75 and 12.25 VDC and has an average draw of 50 mA. Therefore, the reader<br />

can be directly powered from the reader interface modules. The reader can output both standard Clock and<br />

Data or standard Wiegand data. To get proper LED functionality, the reader must be set up for 2-wire LED<br />

mode. Please follow the diagrams for proper wiring of the reader.<br />

19.2.1 <strong>Wiring</strong> the BAS-1300<br />

TYPICAL SOFTWARE SETTINGS<br />

1. <strong>Reader</strong> Type = WIEGAND/PROX<br />

2. Keypad = NO KEYPAD<br />

3. LED Mode = 2-WIRE LED CONTROL<br />

Terminal on Back<br />

of <strong>Reader</strong><br />

Single <strong>Reader</strong><br />

Interface Module<br />

GND<br />

5-12 VDC<br />

Ground<br />

Clock / D0<br />

Data / D1<br />

Green LED<br />

Red LED<br />

(8)<br />

(7)<br />

(6)<br />

(5)<br />

(4)<br />

(3)<br />

(2)<br />

(1)<br />

INTEGRATED<br />

ENGINEERING<br />

BZR<br />

LED<br />

CLK/D1<br />

DATA/D0<br />

VO<br />