Alternative Reader Wiring Guide - Best Access Systems
Alternative Reader Wiring Guide - Best Access Systems
Alternative Reader Wiring Guide - Best Access Systems
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Keri <strong>Systems</strong> <strong>Reader</strong>s<br />
17.1.2 <strong>Wiring</strong> the BAS-1320<br />
The P-400, P-600, and P-700 require a separate 12 VDC power source. They cannot be powered from the<br />
panel.<br />
Dual <strong>Reader</strong> Interface Module<br />
READER 1<br />
VO 12 VDC +<br />
LED<br />
BZR<br />
D1/CLK<br />
D0/DATA<br />
SOFTWARE SETTINGS<br />
1. <strong>Reader</strong> Type = Wiegand/Prox<br />
2. Jumper J4 must be set to 12 VDC<br />
3. LED Mode = Single Wire LED Control<br />
4. Use Unregulated Mode for jumper J2<br />
Silver - Shield<br />
Green - Data 0<br />
Brown -Single LED<br />
Cascade <strong>Reader</strong> /<br />
Sierra <strong>Reader</strong><br />
GND<br />
Red - Power<br />
Black - Ground<br />
READER 2<br />
VO<br />
LED<br />
BZR<br />
D1/CLK<br />
Blue - Beeper<br />
Orange - not used<br />
White - Data 1<br />
D0/DATA<br />
GND<br />
The current draws for each reader are as follows:<br />
P-300: 80mA<br />
P-400: 90mA<br />
P-500: 80mA<br />
P-600: 100mA<br />
P-700: 285mA<br />
82 — revision 7