CONCEPTUAL DESIGN January 9, 2009<br />

<strong>Emeryville</strong> <strong>Center</strong> <strong>of</strong> <strong>Community</strong> <strong>Life</strong><br />

24. Clock, Bell, Intercom System for classrooms/school Admin.<br />

25. Emergency power distribution for the Facility.<br />

C. Electric service and distribution equipment:<br />

1. A new 4000 Amp, 277/480 Volt, 3-Phase, 4-Wire electric service shall be<br />

obtained to serve the building.<br />

2. A new Main switchboard shall be installed in the main electric room, or installed<br />

outside the building adjacent to the PG&E transformer. The Main Switchboard<br />

shall be rated at 4000A, 277/480V, 3PH 4W with an incoming Bus Duct<br />

section, a meter/main section, and a full-height distribution section. The main<br />

switchboard and all devices in the main switchboard shall be braced for and<br />

rated to interrupt the available utility company fault current at the point <strong>of</strong><br />

service (to be determined by the utility company), assume 65K AIC.<br />

3. The existing Gym Building panelboards will need to be back feed from the new<br />

main switchboard.<br />

4. All switchgear and distribution equipment throughout the project shall be<br />

seismically braced.<br />

5. Large HVAC system loads shall be fed directly from the main switchboard<br />

distribution section.<br />

6. Smaller HVAC system loads shall be fed from dedicated HVAC system<br />

electrical branch panelboards.<br />

7. Fluorescent lighting shall be fed from 277/480V branch panelboards, via low<br />

voltage relay lighting control panels.<br />

8. Computer, telephone, data communications, TV, audio-visual, and other<br />

sensitive electronic loads shall be fed through dedicated receptacles located as<br />

required throughout the facility. These sensitive loads shall be connected to<br />

dedicated 120/208V 3PH 4W "clean" power branch circuit panelboards located<br />

in the main electrical room and satellite electrical rooms. "Clean" power panels<br />

shall be equipped with integral transient voltage surge suppression systems.<br />

9. Neutral bussing and conductors for distribution equipment and TVSS protected<br />

branch panels shall have 200% rated neutrals to accommodate for harmonic<br />

currents generated by electronic power supplies.<br />

10. Branch circuit panels shall be general-purpose type, surface mounted with<br />

bolt-on type circuit breakers.<br />

Outline Specifications- 69