CONCEPTUAL DESIGN January 9, 2009<br />

<strong>Emeryville</strong> <strong>Center</strong> <strong>of</strong> <strong>Community</strong> <strong>Life</strong><br />

building.<br />

c. Ballfield Lighting - 000Lighting for the Ball fields will be provided, designed<br />

to current I.E.S. standards for <strong>Community</strong> <strong>Center</strong> and High School sporting<br />

applications. Area pole mounted flood lights will be used to light the ball<br />

fields with house side shields to limit the amount <strong>of</strong> light spill <strong>of</strong>f the property.<br />

The lighting will be zoned via control groups to allow for selective control <strong>of</strong><br />

the ball field lighting. The poles may also be used for public address<br />

speakers.<br />

E. Power and Signal<br />

1. Floor Outlet Boxes:<br />

a. A system <strong>of</strong> flush mounted floor power and signal boxes shall be installed<br />

throughout the facility to provide power, telephone, and data needs. The<br />

boxes will be concealed service type with 120Volt outlets and<br />

telephone/data outlets.<br />

2. Branch Circuits:<br />

a. All lighting loads shall be connected to circuit breakers in the 277/480V<br />

branch circuit panelboards via the lighting control relay panels.<br />

b. All convenience power loads shall be connected to circuit breakers in the<br />

120/208V branch circuit panelboard.<br />

c. All computer power loads shall be connected to circuit breakers in the<br />

120/208V “clean” power branch circuit panelboards (with TVSS<br />

protection).<br />

d. Large Mechanical loads shall be connected to 480V-3 phase distribution<br />

breakers in the Main Switchboard.<br />

e. Branch circuit conductors shall be minimum #12. Minimum conduit size<br />

shall be 1/2".<br />

3. Fire Alarm System:<br />

a. A new facility fire alarm system shall be provided for the complete<br />

building and shall be State and Local Fire Marshal approved, fully<br />

addressable, class B wiring throughout, with emergency battery backup<br />

as required by code to provide sixty hour power back up supply while<br />

under load.<br />

Outline Specifications- 73