1. SAFETY SYSTEMS/INTERLOCKS (CONTD.)<br />

S.<br />

No.<br />

Safety<br />

system/<br />

Interlock<br />

Test<br />

conducted<br />

Expected response of<br />

control system<br />

Observed<br />

response<br />

of<br />

control<br />

system<br />

4.<br />

Service keyes<br />

at different<br />

locations(to be<br />

tested<br />

separately)<br />

Operated to<br />

select<br />

maintenance<br />

position<br />

1. Emergency alarm should sound,<br />

message to be displayed on the<br />

monitor and a hard copy to be<br />

obtained<br />

2. Source, if exposed should lower and<br />

the conveyor should stop, if ON.<br />

3. Search should get cancelled<br />

4. Search can not be started or<br />

conducted if the emergency persists<br />

1. Emergency alarm should sound,<br />

message to be displayed on the<br />

monitor and a hard copy to be<br />

obtained<br />

2. Source, if exposed should lower and<br />

the conveyor should stop, if ON.<br />

3. Search should get cancelled<br />

4. Search can not be started or<br />

conducted if the emergency persists<br />

1. Emergency alarm should sound,<br />

message to be displayed on the<br />

monitor and a hard copy to be<br />

obtained<br />

2. Source, if exposed should lower and<br />

the conveyor should stop, if ON.<br />

3. Search can not be started or<br />

conducted if the emergency persists<br />

1. Message to be displayed on the<br />

monitor and a hard copy to be<br />

obtained<br />

2. Emergency alarm should sound<br />

3. Source if exposed should lower and<br />

the conveyor should stop, if ON.<br />

4. Search can not be started or<br />

conducted if the emergency persists<br />

5. Hydraulic motor should stop.<br />

5.<br />

Source raise<br />

wire rope<br />

tension<br />

Simulated by<br />

actuating the<br />

limit switches<br />

which sense<br />

the rope<br />

stretch and<br />

break<br />

condition<br />

6.<br />

Cell exhaust air<br />

flow<br />

Simulated the<br />

condition by<br />

stopping the<br />

exhaust fan<br />

7.<br />

Hydraulic oil<br />

level low<br />

Simulated by<br />

manually<br />

actuating the<br />

oil level<br />

switch<br />

99