3.5.1.4 Procurement of Source/ Equipment<br />

In order to carry out telegamma radiation therapy procedures using sealed<br />

radioisotopes, the applicant should first submit an application to obtain consent<br />

<strong>for</strong> procurement of source or the equipment with source. The applicant should<br />

ensure be<strong>for</strong>e procurement that the telegamma equipment is type approved.<br />

In case the equipment is not type approved, the local manufacturer/local<br />

supplier should submit the documents to AERB demonstrating the compliance<br />

with the applicable national/international standards and the type approval<br />

procedures as per subsection .3.18.1 shall be followed.<br />

Prior to the procurement of the source or equipment with source the applicant<br />

should have the following:<br />

(i)<br />

(ii)<br />

(iii)<br />

(iv)<br />

(v)<br />

(vi)<br />

Radiological safety officer (RSO)<br />

Personnel monitoring devices<br />

Protection level dosimeters<br />

<strong>Radiation</strong> protection manual/emergency preparedness plans and<br />

procedures (EPP)<br />

Room constructed as per AERB approved layout plan.<br />

Provisions/commitment <strong>for</strong> safe disposal of spent/ disused sources.<br />

The radiation protection manual should be as per Appendix 7E.<br />

Based on review of the Application, AERB may issue Consent <strong>for</strong> the<br />

procurement of source or equipment with source.<br />

The Application <strong>for</strong>mat <strong>for</strong> obtaining Consent <strong>for</strong> procurement/import of<br />

source or telegamma therapy equipment with source is given in<br />

Annexure 21.<br />

In case of telegamma therapy units containing depleted Uranium, details<br />

regarding the same also need to be furnished as given in Annexure 21.<br />

3.5.1.5 Commissioning and Operation<br />

Be<strong>for</strong>e the grant of commissioning and operation licence, the Applicant is<br />

required to<br />

(i)<br />

(ii)<br />

(iii)<br />

Evaluate the per<strong>for</strong>mance of the type-approved telegamma unit and<br />

prepare acceptance test report and submit to AERB.<br />

Prepare and implement the quality assurance programme.<br />

Prepare and implement the <strong>Radiation</strong> Protection Manual as per<br />

Appendix 7E.<br />

These documents would be reviewed by AERB prior to grant of Licence <strong>for</strong><br />

commissioning and operation.<br />

36