IP 55 Modular Cabinets
IP 55 Modular Cabinets
IP 55 Modular Cabinets
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
PTR SECTIONS - TRANSFORMER DOOR SECTION<br />
PTR - TRANSFORMER SECTION<br />
The transformer support section is an<br />
accessory that is attached to the perimeter<br />
slots of the bottom, according to the<br />
direction of width or depth of the cabinet,<br />
especially built to support and attach the<br />
transformer unit, with the sliding block.<br />
It is particularly robust, easy to assembly<br />
and adjust for adaptation to the various<br />
types of transformers. The L or P dimension<br />
respectively indicates placement<br />
according to the width or depth. This section<br />
is always used in couples, even if only<br />
one code is indicated in the table.<br />
GRAPH SHOWING ADMISSIBLE LOAD FOR THE PTR SECTION<br />
M (Kg)<br />
350<br />
300<br />
250<br />
200<br />
150<br />
100<br />
50<br />
400 600 800 1000 1200 1400 1600<br />
CODE<br />
Width of<br />
cabinet<br />
L/P (mm)<br />
Fig. 135.1<br />
PTR..L: TRANSFORMER SUPPORT, APPLICABLE IN WIDTH<br />
Characteristic dimensions<br />
L Block<br />
PTR600L 600 580 PTR680<br />
PTR800L 800 780 PTR680<br />
PTR1000L 1000 980 PTR680<br />
PTR1200L 1200 1180 PTR680<br />
PTR1400L 1400 1380 PTR680<br />
PTR1600L 1600 1580 PTR680<br />
Kit of 4 ea. PTR681 blocks<br />
PTR681<br />
Dimensions in mm<br />
21 CATALOGUE<br />
Block<br />
PTR680<br />
L/P<br />
Fig. 135.2<br />
CODE<br />
Key to graph:<br />
The maximum transformer load mass<br />
can be obtained from the graph, according<br />
to the nominal L or P value of the<br />
transformer section. It should be born<br />
in mind that this load refers to two<br />
parallel sections without intermediate<br />
supports and without dynamic loads. If<br />
there are intermediate supports, the<br />
load corresponds to a value of L or P<br />
equal to the distance between the supports.<br />
Example:<br />
- For a PTR800L section having a nominal<br />
length of 800 mm, the mass M of<br />
the maximum load amounts to 150 kg;<br />
- For a PTR1000P section having a nominal<br />
depth of 1000 mm, the mass M of<br />
the maximum load amounts to 125 kg;<br />
PTR..P: TRANSFORMER SUPPORT, APPLICABLE IN DEPTH<br />
BOZZA DI STAMPA<br />
Depth of<br />
the cabinet<br />
Characteristic dimensions<br />
P Block<br />
PTR400P 400 380 PTR680<br />
PTR500P 500 480 PTR680<br />
PTR600P 600 580 PTR680<br />
PTR800P 800 780 PTR680<br />
PTR1000P 1000 980 PTR680<br />
Kit of 4 ea. PTR681 blocks<br />
Dimensions in mm<br />
PTR681<br />
PTR<br />
135