SC-AH; AIR TO WATER HEAT EXCHANGERS<br />
Fig. 169.1<br />
Note:<br />
The note relative to power yield is the<br />
same in CF-P and CST conditioners, with<br />
the difference that the specific yield in the<br />
table shown below refers to a temperature<br />
difference of 25°, respectively, between<br />
the cabinet temperature and the temperature<br />
of the water intake.<br />
SC-AH : DATA ON DESIGN CHARACTERISTICS<br />
CODE<br />
Fig. 169.2<br />
Fig. 169.2 - Example<br />
of operation of an Air<br />
to Water heat exchanger.<br />
Absorbed<br />
power<br />
SC - AH<br />
If the temperature inside the cabinet is<br />
less or equal to the outside temperature,<br />
it is possible to install an Air to Water<br />
heat exchanger, but connection to the<br />
water mains is necessary in this case.<br />
The structure is in RAL 70325 painted<br />
sheet metal, complete with a self-adhesive<br />
gasket; the system of condensation<br />
recovery and control; exchanger pack<br />
with aluminium fins and copper tubing,<br />
radial or axial fans on ball bearings, with<br />
internal thermal protection and a 3 m<br />
long power cable.<br />
Available on request:<br />
Adjustment thermostat with water electro<br />
valve.<br />
Power<br />
Absorbed<br />
Voltage<br />
Dimensions:<br />
H x W x D<br />
Weight<br />
W V - Hz A mm Kg<br />
SC - AH / 0656 35 230 - 50/60 0,21 404x308x114 9<br />
SC - AH / 1<strong>55</strong>6 80 230 - 50/60 0,36 925x400x205 20<br />
SC - AH / 2<strong>55</strong>6 80 230 - 50/60 0,38 925x400x205 21<br />
SC - AH / 5050 1<strong>55</strong> 230 - 50/60 0,7 1101x501x300 39<br />
SC - AH / 10056 310 230 - 50/60 1,4 2000x800x400 90<br />
SC - AH / 10050-4 310 400/440 - 50/60 0,8 2000x800x400 90<br />
SC - AH / 14000 170 230 - 50/60 0,78 2000x800x600 90<br />
SC - AH / 14000-4 170 400/440 - 50/60 0,5 2000x800x600 90<br />
CODE<br />
Loss of load<br />
Cabinet Cabinet<br />
Specific Fan Air Water Water<br />
Water<br />
on water<br />
Working side<br />
yield Capacity capacity pressure<br />
connection<br />
side<br />
limit protection<br />
Nose level<br />
W m 3 /h l/h kPa kPa inch °C <strong>IP</strong> dB(A)<br />
SC - AH / 0656 870 330 150 500 2 3/8 10 ÷ 50 <strong>IP</strong> <strong>55</strong> 58<br />
SC - AH / 1<strong>55</strong>6 2200 575 150 500 2 1/2 10 ÷ 50 <strong>IP</strong> <strong>55</strong> 58<br />
SC - AH / 2<strong>55</strong>6 3100 860 500 500 63 1/2 10 ÷ 50 <strong>IP</strong> <strong>55</strong> 58<br />
SC - AH / 5050 6700 1450 860 500 40 1/2 10 ÷ 50 <strong>IP</strong> <strong>55</strong> 58<br />
SC - AH / 10056 12500 2900 1440 800 90 3/4 10 ÷ 50 <strong>IP</strong> 54 60<br />
SC - AH / 10050-4 12500 2900 1440 800 90 3/4 10 ÷ 50 <strong>IP</strong> 54 60<br />
SC - AH / 14000 17500 2365 2520 600 121 3/4 10 ÷ 50 <strong>IP</strong> 54 76<br />
SC - AH / 14000-4 17500 2365 2520 600 121 3/4 10 ÷ 50 <strong>IP</strong> 54 76<br />
BOZZA DI STAMPA<br />
Note: The templates for the exchangers are supplied on request.<br />
21 CATALOGUE<br />
169