118 en | Appendices <strong>Fire</strong> <strong>Alarm</strong> <strong>Control</strong> <strong>Panels</strong>4/2 POINT REPORTSPOINT 6 D2: 6POINT 7 D2: 7POINT 8 D2: 8POINT 9 D2: 9POINT 10 D2: 04/2 RPT CODSSYSTM IN TST: 33SYS TEST RST: 37SILENCE:9FFIRE DRILL: 33FIRE DRL RST: 37OPEN RST RPT:9FLOW BATTERY: 69LOW BATT RST: 79AC FAILURE: 60AC FAIL RST: 70TEST REPORT: 30OFF NORM TST: 33PHONE 1 TRBL: 31PN 1 TRB RST: 35PHONE 2 TRBL 32PN 2 TRB RST: 36SYSTEM TROUB: 33SYS TRB RST: 37MultiplexMUX BUS TYPE:2 CLASS B10.5Appendix E: Phone Monitor Troubleshooting10.5.1COMM FLT/DATA LOSTA common cause of this fault condition is failing to program Phone/IP Number 2 or AccountNumber 2 while some reports are directed to Phone/IP 2 Backup reports are still made toPhone/IP Number 1. This message warns the installer that Phone/IP Number 2 is not availableif it is needed.2012.08 | 04 | F01U008458 Installation and Operation Manual <strong>Bosch</strong> <strong>Security</strong> System, Inc.