<strong>Fire</strong> <strong>Alarm</strong> <strong>Control</strong> <strong>Panels</strong> Connection | en 31Unsupervised:Switched unsupervised:1 Relay 1 4 Earth ground2 Relay 2 5 Smoke detector3 Relay 3Input Points 1-4:(supervised) Points are intended for connection of normally-open/normally-closed alarmcontacts. They may also be used for compatible two-wire smoke detectors. All EOL resistorsare 2.21 kΩ, P/N: 25899 <strong>Bosch</strong>, UL listed. Initiating devices are Class B, Style B or Class A,Style D. Two‐wire Compatibility Identifier "A".iNotice!For connection to listed power limited Class 2 or Class 3 sources only. Contacts rated at5.0 A, 24 V.iNotice!Smoke Power: 24 V, 1.0 A maimum (filtered).For compatible devices, see also Technogram P/N: F01U0790.Figure 5.5: Telephone lines 1 and 21 Phone Line 2 (supervised) 2 Phone Line 1 (supervised)<strong>Bosch</strong> <strong>Security</strong> System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458