Appendix BInstalling and Configuring the ControlNetCommunications DriverThe examples using ControlNet in this manual were performed with a1784-KTCX15 communication interface card installed in the personalcomputer that was used as a programming terminal. This appendixdescribes how to install and configure the 1784-KTCX15 card.Installing the 1784-KTCX15Communication InterfaceCardPerform the following steps to install the 1784-KTCX15 card in yourpersonal computer.1. Set the card’s base memory address location on switches S1 and S2.MoreFor detailed information oninstalling the 1784-KTCX15, referto the ControlNet CommunicationInterface Card InstallationInstructions, publication number1784-5.33.Front of SwitchesD000:0000Factory-set address(recommended setting)S2up (1)down (0)S1Front Viewdown (0)up (1)Side View2. Set the card’s base I/O space address location on switch S3.Front of Switches240h shown(adjust for your system)S3up (1)down (0)Front Viewdown (0)up (1)Side View1 Publication <strong>1771</strong>-<strong>6.5.132</strong> - June 2000