12.11.2013 Views

Masoneilan Products SVI II ESD - GE Energy

Masoneilan Products SVI II ESD - GE Energy

Masoneilan Products SVI II ESD - GE Energy

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>GE</strong> <strong>Energy</strong><br />

<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Quick Start<br />

Necessary Precautions<br />

To avoid injury or affecting the process when installing or replacing a PST<br />

controller on a control valve, ensure that:<br />

If the valve is located in a hazardous area make sure the area has been<br />

certified as safe or that all electrical power to the area has been<br />

disconnected before removing any covers or disconnecting any leads.<br />

Shut off air supply to the actuator and to any valve mounted equipment.<br />

Ensure the valve is isolated from the process by either shutting off the<br />

process or using bypass valves for isolation. Tag shutoff or bypass<br />

valves to guard against a turn-on while work is in progress.<br />

Bleed air from actuator and check that valve is in its de-energized<br />

position.<br />

It is now safe to disconnect and remove any valve mounted equipment that is<br />

being replaced.<br />

<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Components<br />

Figure 2 provides a drawing of the <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> components.<br />

<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Cover<br />

<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Assembled<br />

Pneumatic Train and<br />

Cover (I/P Module, Relay)<br />

I/P<br />

Manifold<br />

Electronics<br />

Module<br />

Pneumatic Relay<br />

Figure 2 <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Components<br />