Specifications and<br />
Hazardous Location Installation<br />
Table 17 Pneumatics Double Acting Standard Flow (Continued)<br />
Air Supply Dry, oil-free, 5 micron filtered air see ISA S7.3<br />
Air Consumption<br />
for Double Acting<br />
0.424 scfm (12 slm) at 30 psi (2.1 bar, 207 kPa) supply<br />
0.565 scfm (16 slm) at 60 psi (4.14 bar, 414 kPa) supply<br />
0.847 scfm (24 slm) at 90 psi (6.21 bar, 621 kPa) supply<br />
1.06 scfm (30 slm) at 120 psi (8.28 bar, 828 kPa) supply<br />
Air Supply Failure<br />
Loss of Input<br />
Signal<br />
Positioner cannot control the failure position of an actuator<br />
without a spring. The actuator can, under different conditions, fail<br />
in place, fail open, or fail close. In cases where the valve must fail<br />
to a required position additional control equipment is required.<br />
Output 1 drops to low pressure.<br />
Output 2 rises to supply pressure.<br />
Hazardous Location Installation<br />
The following pages provide the agency approved installation procedure for<br />
hazardous locations (ES-727).<br />
NOTE<br />
The installation procedure is accurate at time of print. For<br />
further hazardous installation information please consult the<br />
factory.<br />
65