<strong>GE</strong> <strong>Energy</strong><br />

7. Scroll to line 6 “EXAMINE”, press -><br />

8. Scroll down to line 5 read status.<br />

9. Read message.<br />

10. Press OK<br />

<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Quick Start<br />

11. Repeat OK to read all messages until the display returns to “read status”<br />

12. Scroll down to line 6 clear status, press -><br />

13. If clear fault codes not completed appears, press OK and read the<br />

message (Position Error, for example) or go to the troubleshooting guide.<br />

14. Correct the problem (Is the air supply on?), and then go to clear status until<br />

Clear Fault codes Completed appears.<br />

15. Press OK.<br />

Diagnostics<br />

The <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> provides two types of diagnostic information; the continuous<br />

diagnostics that require no user configuration for which no valve movement<br />

occurs and Partial Stroke Testing (PST) diagnostics that you can configure and<br />

run at any time. You can also manually run a proof test (see page 11).<br />

Partial Stroke Test Diagnostics<br />

The <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> is capable of partially stroking the valve to detect failures in the<br />

final control element assembly. The PST is configured using the pushbutton<br />

display or through ValVue <strong>ESD</strong>. Upon detection of a failure or deviation from the<br />

user configurable conditions the annunciation channel SW 1 sets its state to low.<br />

The PST can be configured to start automatically or can be initiated through<br />

setting the current input to 16.4 mA. +/- 0.1mA, local control panel pushbutton, or<br />

initiated locally by an operator. When configured to run automatically or when<br />

initiated through a safety rated logic solver, additional diagnostic credit can be<br />

taken for the PST.<br />

In addition to the safety rated I/O, HART communications are available to provide<br />

additional information on the <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> status. Additional diagnostic functions<br />

include:<br />

With ASD or A/DSD modes, the device is capable of capturing and<br />

storing the shutdown event when the safety function is engaged and / or<br />

when the valve is positioned using the control signal (4-20 mA or <br />

0-24 VDC).<br />

The <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> can provide general information of the device’s sensor<br />

health (Temperature, Actuator Pressure, Air supply, Current, etc.).<br />

Capable of annunciating faults resulting from a PST.<br />