Masoneilan Products SVI II ESD - GE Energy
Masoneilan Products SVI II ESD - GE Energy
Masoneilan Products SVI II ESD - GE Energy
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>GE</strong> <strong>Energy</strong><br />
<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Quick Start<br />
Checking the Electronic Module Connections<br />
WARNING<br />
Do not remove the instrument cover or connect to an<br />
electrical circuit in a Hazardous Area unless the power is<br />
disconnected.<br />
All connections to electronic module in the <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> are made through the<br />
terminal board. There are three versions of the terminal board, dependent on the<br />
configuration you have; ASD, DSD, or A/DSD. The <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> terminal board has<br />
a terminal block with cage clamp connectors. Confirm that all applicable<br />
connections to the electronics module connectors are correct. Not all options are<br />
available for every model. Refer to Table 5 for available functionality.<br />
I/O ON <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong><br />
Table 5<br />
<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Models and Functionality<br />
Usage<br />
<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong><br />
ASD Analog<br />
Safety Demand<br />
<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong><br />
DSD Discrete<br />
Safety Demand<br />
<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong><br />
A/DSD Analog<br />
Power with<br />
Discrete Safety<br />
Demand<br />
Analog In (4-20mA) Safety Trip Signal +<br />
HART + Analog<br />
PST<br />
Not Used Device Power +<br />
Analog PST +<br />
HART<br />
<strong>ESD</strong> In (0-24 VDC) Not Used Safety Trip Signal +<br />
HART<br />
Safety Trip Signal<br />
SW1 (1A, 24 VDC) <strong>ESD</strong> Status (ON =<br />
OK)<br />
<strong>ESD</strong> Status (ON =<br />
OK)<br />
<strong>ESD</strong> Status (ON =<br />
OK)<br />
SW2 (1A, 24 VDC) Configurable Status Configurable Status Configurable<br />
Status<br />
DI (switch input) Unlatch (1) Unlatch (1) Unlatch (1)<br />
PV (1-5 VDC)<br />
Read Tight Shutoff<br />
Flow (2)<br />
Read Tight Shutoff<br />
Flow (2)<br />
Read Tight Shutoff<br />
Flow (2)<br />
Local LCD / Buttons<br />
<strong>ESD</strong> Status Local<br />
PST<br />
<strong>ESD</strong> Status Local<br />
PST<br />
<strong>ESD</strong> Status Local<br />
PST<br />
(1) Latching is software configurable.<br />
(2) 1 - 5 VDC variable is sent using HART command #3 as the variable TV.<br />