<strong>GE</strong> <strong>Energy</strong><br />
<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Quick Start<br />
HAZARDOUS LOCATION<br />
SEE 7.1, 7.2<br />
Equi-Potential<br />
Switch<br />
(See<br />
7.3.5)<br />
NON-HAZARDOUS LOCATION - UNSPECIFIED EXCEPT<br />
THAT BARRIERS MUST NOT BE SUPPLIED FROM NOR<br />
CONTAIN UNDER NORMAL OR ABNORMAL CONDITIONS A<br />
SOURCE OF POTENTIAL WITH RESPECT TO EARTH IN<br />
EXCESS OF 250 VOLTS RMS OR 250 VOLTS DC<br />
Shunt Zener Diode Safety Barrier<br />
Controller Output Type (See 7.3.6)<br />
Optional Hand Held<br />
Communicator (See 7.3)<br />
3<br />
4<br />
1<br />
2<br />
24 VDC Trip<br />
Signal from DCS<br />
(A/DSD & DSD<br />
ONLY)<br />
<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong><br />
PV 1-5VDC 4-20mA OUT SW 1, SW 2 4-20mA IN 24 VDC IN DI<br />
+<br />
-<br />
+<br />
-<br />
+<br />
-<br />
+<br />
-<br />
+<br />
-<br />
Optional Hand Held<br />
Communicator (See 7.3)<br />
Optional<br />
Field Load<br />
3<br />
4<br />
3<br />
4<br />
3<br />
4<br />
3<br />
4<br />
250Ω<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
LOAD<br />
Optional Hand Held<br />
Communicator (See 7.3)<br />
4-20 mA Trip<br />
Signal from DCS<br />
(ASD & A/DSD<br />
ONLY)<br />
Shunt Zener Diode Safety Barrier -<br />
Controller Output Type (See 7.3.1,<br />
7.3.3)<br />
24 VDC from<br />
DCS<br />
To DCS DI<br />
Shunt Zener Diode Safety<br />
Barrier Switch Type Barrier<br />
(See 7.3.4)<br />
24 VDC from<br />
DCS<br />
1-5VDC To<br />
DCS<br />
Transmitter Barrier Type w/<br />
Internal or External Sense<br />
Resistor (See 7.3.2)<br />
Shunt Zener Diode Safety<br />
Barrier Controller Output Type<br />
(See 7.3.1, 7.3.3)<br />
1-5VDC To<br />
DCS<br />
Optional I.S.<br />
TRANSMITTER<br />
+<br />
-<br />
Cable Shield<br />
Each intrinsically safe cable must include a<br />
grounded shield or be run in a separate grounded<br />
metal conduit<br />
3<br />
250Ω<br />
4<br />
24 VDC from<br />
1<br />
Control<br />
System<br />
2<br />
Shunt Zener Diode Safety<br />
Barrier Transmitter Type w/<br />
Internal or External Sensing<br />
Resistor<br />
Equi-Potential (See 7.3.3)<br />
Doc Number<br />
ES-727<br />
Written By P.Levesque 13DEC2006<br />
Revision M ADR-003666 04/19/12<br />
Checked T.Kabir 10JAN2007<br />
Filename ES-727.DOC Page 7 of 11 Approved T. Kabir 10JAN2007<br />