Masoneilan Products SVI II ESD - GE Energy
Masoneilan Products SVI II ESD - GE Energy
Masoneilan Products SVI II ESD - GE Energy
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Specifications and<br />
Physical and Operational<br />
Table 15 System Connectivity (Continued)<br />
HART Information<br />
DD for Handheld<br />
HART CMD #3<br />
HART rev 5, ManufacturerID 0065, DeviceID 00CB<br />
Yes, for HH375<br />
PV= Valve Position 0-100% SV=Actuator Net<br />
Pressure<br />
TV=PV Input 1-5 VDC<br />
Table 16 Pneumatics Single Acting Standard Flow<br />
Air Supply<br />
Action<br />
Supply Pressure<br />
Dry, oil-free, 5 micron filtered air (See ISA S7.3)<br />
Direct<br />
30 -120 psi max. (2.07 - 8.27 bar, 207 - 827 kPa)<br />
Regulate 10 psi above actuator spring range. Do<br />
not exceed actuator rating.<br />
Air Delivery - Single Acting<br />
Relay<br />
11.55 scfm (325 slm) filling, 14.12 scfm (400 slm)<br />
venting at 30 psi (2.1 bar, 207 kPa) supply<br />
19.25 scfm (545 slm) filling, 23.48 scfm (665 slm)<br />
venting at 60 psi (4.14 bar, 414 kPa) supply<br />
27 scfm (765 slm) filling, 32.84 scfm (930 slm)<br />
venting at 90 psi (6.21 bar, 621 kPa) supply<br />
34.6 scfm (980 slm) filling, 42.37 scfm (1200 slm)<br />
venting at 120 psi (8.28 bar, 828 kPa) supply<br />
Air Capacity<br />
(flow coefficient)<br />
Loading CV = 0.57<br />
Venting CV = 0.53<br />
63