Specifications and<br />

Physical and Operational<br />

Table 15 System Connectivity (Continued)<br />

HART Information<br />

DD for Handheld<br />

HART CMD #3<br />

HART rev 5, ManufacturerID 0065, DeviceID 00CB<br />

Yes, for HH375<br />

PV= Valve Position 0-100% SV=Actuator Net<br />

Pressure<br />

TV=PV Input 1-5 VDC<br />

Table 16 Pneumatics Single Acting Standard Flow<br />

Air Supply<br />

Action<br />

Supply Pressure<br />

Dry, oil-free, 5 micron filtered air (See ISA S7.3)<br />

Direct<br />

30 -120 psi max. (2.07 - 8.27 bar, 207 - 827 kPa)<br />

Regulate 10 psi above actuator spring range. Do<br />

not exceed actuator rating.<br />

Air Delivery - Single Acting<br />

Relay<br />

11.55 scfm (325 slm) filling, 14.12 scfm (400 slm)<br />

venting at 30 psi (2.1 bar, 207 kPa) supply<br />

19.25 scfm (545 slm) filling, 23.48 scfm (665 slm)<br />

venting at 60 psi (4.14 bar, 414 kPa) supply<br />

27 scfm (765 slm) filling, 32.84 scfm (930 slm)<br />

venting at 90 psi (6.21 bar, 621 kPa) supply<br />

34.6 scfm (980 slm) filling, 42.37 scfm (1200 slm)<br />

venting at 120 psi (8.28 bar, 828 kPa) supply<br />

Air Capacity<br />

(flow coefficient)<br />

Loading CV = 0.57<br />

Venting CV = 0.53<br />