Masoneilan Products SVI II ESD - GE Energy
Masoneilan Products SVI II ESD - GE Energy
Masoneilan Products SVI II ESD - GE Energy
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>GE</strong> <strong>Energy</strong><br />
<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Quick Start<br />
4. On vacuum service, the valve shaft may be drawn into the body by the<br />
vacuum acting on the shaft, but the magnetic coupling must be assembled<br />
flush with the mounting bracket with the shaft pulled fully out to its thrust<br />
bearing. Check that the endplay from the vacuum position to the fully<br />
extended position is less than 0.06 in. (1.524 mm)<br />
5. Slide the magnet holder into the extension shaft. The location of the magnets<br />
is in the ring of the magnet holder. The magnetic axis is the imaginary line<br />
through the center of both magnets.<br />
6. Rotate the magnet holder so that the magnet axis is vertical when the valve is<br />
in the closed position.<br />
7. Align the end of the magnet holder flush with the end of the mounting bracket.<br />
Secure the magnet holder with two M6 set screws.<br />
8. Slide the V-Seal over the magnet holder.<br />
9. Secure the <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> onto the mounting bracket using four M6 x 20 mm<br />
Socket Head Cap Screws.<br />
10. Ensure no interference exists with the position sensor protrusion.<br />
11. Ensure that the V-Seal makes contact with the skirt around the position sensor<br />
protrusion on <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> housing.<br />
18