4. On vacuum service, the valve shaft may be drawn into the body by the<br />

vacuum acting on the shaft, but the magnetic coupling must be assembled<br />

flush with the mounting bracket with the shaft pulled fully out to its thrust<br />

bearing. Check that the endplay from the vacuum position to the fully<br />

extended position is less than 0.06 in. (1.524 mm)<br />

5. Slide the magnet holder into the extension shaft. The location of the magnets<br />

is in the ring of the magnet holder. The magnetic axis is the imaginary line<br />

through the center of both magnets.<br />

6. Rotate the magnet holder so that the magnet axis is vertical when the valve is<br />

in the closed position.<br />

7. Align the end of the magnet holder flush with the end of the mounting bracket.<br />

Secure the magnet holder with two M6 set screws.<br />

8. Slide the V-Seal over the magnet holder.<br />

9. Secure the <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> onto the mounting bracket using four M6 x 20 mm<br />

Socket Head Cap Screws.<br />

10. Ensure no interference exists with the position sensor protrusion.<br />

11. Ensure that the V-Seal makes contact with the skirt around the position sensor<br />

protrusion on <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> housing.<br />