<strong>GE</strong> <strong>Energy</strong><br />
<strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> Quick Start<br />
Electrical Connection Guidelines<br />
When making the <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> electrical connections, follow these guidelines:<br />
1. The <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> device is available in two control signal configurations: 20 mA<br />
or 24 VDC.<br />
2. Provide sufficient electrical isolation between adjacent signal lines and<br />
between signal lines and ground for all wiring.<br />
3. Use stranded 14 to 22 AWG (or equivalent gauge and flexibility).<br />
4. Use conduit sealant to prevent condensation from entering the enclosure and,<br />
in Class 1 Div. 2 conditions to prevent hazardous gasses and vapors from<br />
migrating through the conduit to the control room or an open ignition source.<br />
5. Wire according to the National Electrical Code (ANSI-NFPA 70) or other<br />
applicable local codes.<br />
6. The terminal clamps are designed for one wire only; DO NOT attempt to<br />
terminate multiple wires into one terminal.<br />
7. Strip the wires to the recommended length (See product specifications).<br />
8. Ensure all wire stands are fully inserted into the terminal block and no shorts<br />
between adjacent wires on the terminal block are possible.<br />
9. Use care when running signal wiring near to or crossing conduit or wiring that<br />
supplies power to motors, solenoids, lighting, horns, bells, etc. Provide<br />
sufficient electrical isolation and shielding against electro-magnetic<br />
interference from items in the vicinity of the cable run.<br />
10. Run AC power wiring in a separate conduit from DC power. All power wiring to<br />
and from the <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> must be in grounded conduit. Protect outdoor cable<br />
runs against lightning strike.<br />
11. Connect the <strong>SVI</strong> <strong>II</strong> <strong>ESD</strong> to a high quality instrument grade ground sized as<br />
required by local electrical codes. A grounding stud is provided inside the<br />
enclosure.<br />
WARNING<br />
Comply with current national and local regulations for<br />
electrical installation work.<br />
Comply with national and local explosive atmosphere<br />
regulations.<br />
Before carrying out any work on the device, power off the<br />
instrument or make sure that the locale conditions for<br />
potentially explosive atmosphere permit the safe opening of<br />
the cover.<br />
32