Specifications and<br />
Hazardous Location Installation<br />
7.3.5 DI (Digital In) Terminals<br />
The Digital In terminal is suitable for direct connection to a passive switch. No barrier is required.<br />
Connect only to passive (Un-powered) switch.<br />
Table 5, DI Entity Parameters<br />
Uo/Voc Po Ca La<br />
Entity Parameters 6.5 V 194mW 1 uF 2 mH<br />
7.3.6 24 VDC IN (+) and (-)<br />
The 24 VDC IN circuit is connected thru a Controller output type barrier, for example MTL 728.<br />
Table 6, 24 VDC IN Entity Parameters<br />
Vmax Imax Ci Li Pmax<br />
Entity Parameters 30 VDC 125 mA 7 nF 10 uH 900 mW<br />
7.4 Use in Dust Atmospheres<br />
Dust-tight conduit seal must be used when installed in dust hazard environments.<br />
7.5 Safe Guards for I.S. Barriers<br />
A device which has previously been installed without an approved I.S. barrier must NEVER be used<br />
subsequently in an intrinsically safe system. Installing the device without a barrier can permanently<br />
damage the safety related components in the device making the device unsuitable for use in an<br />
intrinsically system.<br />
8 Repair<br />
WARNING: EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR<br />
SUITABILITY FOR USE IN A HAZARDOUS LOCATION<br />
Only <strong>Masoneilan</strong> qualified <strong>ESD</strong> service personnel are permitted to make repairs. The only replacement<br />
part offered for the <strong>ESD</strong> is the display cover.<br />
8.1 COVER (DISPLAY)<br />
Make sure that:<br />
The gasket is seated in the groove in the housing flange.<br />
No wires or retaining cable can be trapped under the cover flange.<br />
The flange area is not corroded and the surface is not scared.<br />
The four cover bolts are securely tightened.<br />
Secure the four cover bolts by applying a torque of 55±5 in-lbs.<br />
Doc Number<br />
ES-727<br />
Written By P.Levesque 13DEC2006<br />
Revision M ADR-003666 04/19/12<br />
Checked T.Kabir 10JAN2007<br />
Filename ES-727.DOC Page 10 of 11 Approved T. Kabir 10JAN2007<br />
Copyright 2006 as an unpublished trade secret. This document and all information herein is the property of Dresser Flow Control,<br />
Dresser, Inc. It is confidential and must not be made public or copied and is subject to return upon demand.<br />
75