Specifications and<br />

Hazardous Location Installation<br />

7.3.5 DI (Digital In) Terminals<br />

The Digital In terminal is suitable for direct connection to a passive switch. No barrier is required.<br />

Connect only to passive (Un-powered) switch.<br />

Table 5, DI Entity Parameters<br />

Uo/Voc Po Ca La<br />

Entity Parameters 6.5 V 194mW 1 uF 2 mH<br />

7.3.6 24 VDC IN (+) and (-)<br />

The 24 VDC IN circuit is connected thru a Controller output type barrier, for example MTL 728.<br />

Table 6, 24 VDC IN Entity Parameters<br />

Vmax Imax Ci Li Pmax<br />

Entity Parameters 30 VDC 125 mA 7 nF 10 uH 900 mW<br />

7.4 Use in Dust Atmospheres<br />

Dust-tight conduit seal must be used when installed in dust hazard environments.<br />

7.5 Safe Guards for I.S. Barriers<br />

A device which has previously been installed without an approved I.S. barrier must NEVER be used<br />

subsequently in an intrinsically safe system. Installing the device without a barrier can permanently<br />

damage the safety related components in the device making the device unsuitable for use in an<br />

intrinsically system.<br />

8 Repair<br />

WARNING: EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR<br />

SUITABILITY FOR USE IN A HAZARDOUS LOCATION<br />

Only <strong>Masoneilan</strong> qualified <strong>ESD</strong> service personnel are permitted to make repairs. The only replacement<br />

part offered for the <strong>ESD</strong> is the display cover.<br />

8.1 COVER (DISPLAY)<br />

Make sure that:<br />

The gasket is seated in the groove in the housing flange.<br />

No wires or retaining cable can be trapped under the cover flange.<br />

The flange area is not corroded and the surface is not scared.<br />

The four cover bolts are securely tightened.<br />

Secure the four cover bolts by applying a torque of 55±5 in-lbs.<br />

Doc Number<br />

ES-727<br />

Written By P.Levesque 13DEC2006<br />

Revision M ADR-003666 04/19/12<br />

Checked T.Kabir 10JAN2007<br />

Filename ES-727.DOC Page 10 of 11 Approved T. Kabir 10JAN2007<br />