10.12.2012 Views

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Conformance to IS 13947 (Part 3) <strong>and</strong> IEC:60947-3<br />

Type Designation �N32 �N63 �N100 �N125<br />

No. of poles 3+Neutral 3+Neutral 3+Neutral 3+Neutral<br />

Neutral Switched Switched Isolable Isolable<br />

Service temperature °C -20 to 50 -20 to 50 -20 to 50 -20 to 50<br />

Rated operational voltage (Ue) V 415 415 415 415<br />

Rated insulation voltage (Ui) V 690 690 690 690<br />

Rated impulse withst<strong>and</strong> voltage(Uimp) kV 888 8<br />

Rated frequency Hz 50-60 50-60 50-60 50-60<br />

Conventional Enclosed thermal current at 40°C A 32 63 100 125<br />

Rated operational current Ie A<br />

AC 20A utilization category 32 63 100 125<br />

AC-21A utilization category 32 63 100 125<br />

AC-22A utilization category 32 63 100 125<br />

AC-23A utilization category 32 63 100 125<br />

DC rating at 220V DC 32 63 100 125<br />

No.of poles in series,utilization category<br />

at rated current 3,DC23A 3,DC23A 2,DC23A 2,DC23A<br />

Rated making capacity (436V, cosØ-0.35) A 320 630 1000 1250<br />

Rated breaking capacity (436V, cosØ-0.35) A 256 504 800 1000<br />

Rated fused short circuit current kA 80 80 100 100<br />

with L&T fuses rating,A /Type Size 32/H� 63/H� 100/HN00 125/HN00<br />

Capacitor duty - 415 V 50-60Hz kVAR 14 29 45 57<br />

Mechanical life (operating cycles) 15000 15000 15000 15000<br />

Terminal capacity (main) mm 2 35 35 95 95<br />

Terminal capacity (neutral) mm 2 35 35 50 50<br />

Terminal screw mm M6X12 M6X12 M8X20 M8X30<br />

Details of fuses available<br />

TECHNICAL DATA<br />

SWITCH DISCONNECTOR �USE �OR DIN TYPE �USES<br />

L&T Type designation H� H� HN HN<br />

Size 14x51 14X51 00 00<br />

Rating of L&T fuses available 2-32 2-63 63-100 63-125<br />

3/4<br />

3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!