Conformance to IS 13947 (Part 3) <strong>and</strong> IEC:60947-3<br />

Type Designation �N200 �N250<br />

No. of poles 3+Neutral 3+Neutral<br />

Neutral Isolable Isolable<br />

Service temperature °C -20 to 50 -20 to 50<br />

Rated operational voltage (Ue) V 415 415<br />

Rated insulation voltage (Ui) V 690 690<br />

Rated impulse withst<strong>and</strong> voltage(Uimp) kV 88<br />

Rated frequency Hz 50-60 50-60<br />

Conventional Enclosed thermal current at 40°C A 200 250<br />

Rated operational current Ie A<br />

AC 20A utilization category 200 250<br />

AC-21A utilization category 200 250<br />

AC-22A utilization category 200 250<br />

AC-23A utilization category 200 250<br />

DC rating at 220V DC 200 250<br />

No.of poles in series,utilization category<br />

TECHNICAL DATA<br />

SWITCH DISCONNECTOR �USE �OR BS TYPE �USES<br />

at rated current 2,DC23A 2,DC23A<br />

Rated making capacity (436V, cosØ-0.35) A 2000 2500<br />

Rated breaking capacity (436V, cosØ-0.35) A 1600 2000<br />

Rated fused short circuit current kA 80 80<br />

with L&T fuses rating,A /Type Size 200,HQ,B2 250,HQ,B3<br />

Capacitor duty - 415 V 50-60Hz kVAR 92 115<br />

Mechanical life (operating cycles) 10000 10000<br />

Terminal capacity (main) mm 2 240 400<br />

Terminal capacity (neutral) mm 2 120 120<br />

Terminal screw mm M10X30 M10X30<br />

3/10<br />

3