10.12.2012 Views

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

8<br />

Sr.<br />

No.<br />

1 1 0.75 2.1 1.21 0.9 - 1.5 MN9 MN9 MN9 4<br />

2 1.5 1.1 2.7 1.6 1.4 - 2.3 MN9 MN9 MN9 6<br />

3 2 1.5 3.5 2.02 1.4 - 2.3 MN9 MN9 MN9 6<br />

4 3 2.25 5 2.88 2 - 3.3 MN9 MN9 MN9 8<br />

5 4 3 6.4 3.7 3 - 5 MN9 MN9 MN9 10<br />

6 5 3.75 7.9 4.6 3 - 5 MN9 MN9 MN9 16<br />

7 6 4.5 9 5.2 4.5 - 7.5 MN9 MN9 MN9 16<br />

8 7.5 5.5 11.2 6.5 4.5 - 7.5 MN9 MN9 MN9 20<br />

9 10 7.5 14.8 8.54 6 - 10 MN9 MN9 MN9 20<br />

10 12.5 9.3 19 11 9 - 15 MN9 MN12 MN12 32<br />

11 15 11 22 12.7 9 - 15 MN12 MN16 MN16 32<br />

12 20 15 29 16.7 14 - 23 MN12 MN25 MN25 40<br />

13 25 18.5 35 20.2 14 - 23 MN16 MN25 MN25 50<br />

14 30 22.5 40 23 20 - 33 MN16 MN25 MN25 63<br />

15 35 26 47 27 20 - 33 MN25 MN32 MN32 63<br />

16 40 30 55 31.8 30 - 50 MN25 MN32 MN32 63<br />

17 45 33.5 60 34.6 30 - 50 MN32 MN45 MN45 80<br />

18 50 37.5 66 38.2 30 - 50 MN32 MN45 MN45 80<br />

19 60 45 80 46.2 30 - 50 MN45 MN65 MN65 100<br />

20 65 48.5 87 50 45 - 75 MN45 MN65 MN65 100<br />

21 70 52 94 54.2 45 - 75 MN45 MN65 MN65 125<br />

22 75 55 100 57.5 45 - 75 MN45 MN80 MN80 125<br />

23 90 67.5 120 69.2 45 - 75 MN80 MN80 MN80 160<br />

24 100 75 135 77.9 66 - 110 MN80 MN95 MN95 160<br />

25 125 90 165 95 66 - 110 MN80 MN140 MN140 200<br />

26 150 110 200 115 90 - 150 MN95 MN140 MN140 250<br />

27 175 130 230 132.8 90 - 150 MN110 MN185 MN185 250<br />

28 200 150 275 159 135 - 225 MN140 MN265 MN265 315<br />

29 240 175 310 178.9 135 - 225 MN140 MN265 MN265 400<br />

30 250 185 325 187 135 - 225 MN140 MN265 MN265 400<br />

31 275 204 360 208 135 - 225 MN265 MN265 MN265 400<br />

32 300 225 385 222 180 - 300 MN265 MN265 MN265 500<br />

33 400 300 500 288.6 180 - 300 MN265 MN325 MN325 500<br />

8/28<br />

SELECTION CHART �OR STAR DELTA STARTERS<br />

MN Relays <strong>and</strong> MN Contactors<br />

(Type “2” Co-ordination, IS13947(Part4/Sec1)/IEC 60947-4-1)<br />

Motor Current at 415V<br />

HP kW Line Phase<br />

Relay Range<br />

A<br />

Star<br />

Contactor<br />

Line Delta<br />

HRC Back-up �use<br />

Rating,A