8<br />

Sr.<br />

No.<br />

1 1 0.75 1.8 1.04 1 - 1.6 ML0 ML0 ML0 4<br />

2 1.5 1.1 2.6 1.5 1 - 1.6 ML0 ML0 ML0 6<br />

3 2 1.5 3.5 2.02 1.5 - 2.5 ML0 ML0 ML0 6<br />

4 3 2.25 5.0 2.88 2.5 - 4 ML0 ML0 ML0 8<br />

5 4 3.0 6.2 3.58 2.5 - 4 ML0 ML0 ML0 10<br />

6 5 3.75 7.5 4.32 4 - 6.5 ML0 ML0 ML0 16<br />

7 6 4.5 9.0 5.2 4 - 6.5 ML0 ML0 ML0 16<br />

8 7.5 5.5 11.0 6.34 6 - 10 ML0 ML0 ML0 20<br />

9 10 7.5 14.0 8.08 6 - 10 ML0 ML0 ML0 20<br />

10 12.5 9.3 18.0 10.4 10 - 16 ML0 ML0 ML0 32<br />

11 15 11.0 21.0 12.1 10 - 16 ML0 ML1 ML1 32<br />

12 20 15.0 28.0 16.2 13 - 21 ML1 ML1.5 ML1.5 40<br />

13 25 18.5 35.0 20.2 13 - 21 ML1 ML1.5 ML1.5 50<br />

14 30 22.5 40.0 23 20 - 33 ML2 ML2 ML2 63<br />

15 35 26.0 47.0 27 20 - 32 ML2 ML2 ML2 63<br />

16 40 30.0 55.0 31.8 28 - 42 ML2 ML3 ML3 63<br />

17 45 33.5 60.0 34.6 28 - 42 ML2 ML3 ML3 80<br />

18 50 37.5 66.0 38.2 28 - 42 ML2 ML3 ML3 80<br />

8/30<br />

SELECTION CHART �OR STAR DELTA STARTERS<br />

ML Relays <strong>and</strong> ML Contactors<br />

(Type “C” Co-ordination IS8544 (Part1)/IEC 292-1, Type “2” Co-ordination IS13947(Part4/Sec1)/IEC 60947-4-1)<br />

Motor Rating Current at 415V, A<br />

HP kW Line Phase<br />

Relay Range<br />

(A)<br />

Star<br />

Contactor<br />

Line Delta<br />

HRC Back-up �use<br />

Rating,A