1 Rating (A) 1600 2000 2500<br />

Type Designation S C H E C H C H<br />

Rated Current (A) 400C In 1600 1600 1600 2000 2000 2000 2500 2500<br />

Rated Operational Voltage (V) 50/60Hz Ue* 415 415 415 415 415 415 415 415<br />

Rated insulation voltage (V), 50/60Hz Ui 1000 1000 1000 1000 1000 1000 1000 1000<br />

No. of poles 3 3/4 3/4 3 3/4 3/4 3/4 3/4<br />

Rated ultimate short circuit Icu<br />

breaking capacity<br />

50/60Hz (kA rms)<br />

380/415/500V 50 50 65 50 55 75 60 75<br />

Rated service short circuit Ics<br />

breaking capcity<br />

50/60Hz (kA rms)<br />

380/415/500V 38 50 65 50 55 75 60 75<br />

Rated short time withst<strong>and</strong> capacity Icw 0.5sec 38 5065 5055 75 60 75<br />

50/60Hz (kA rms) 1sec 38 50 65 50 55 75 60 75<br />

Rated making capacity Icm<br />

50/60Hz (kA peak) 380/415/500V 105 105 143 105 121 165 132 165<br />

Rated impulse withst<strong>and</strong> voltage of main circuit (kV), Uimp 8 8 8 8 8 8 8 8<br />

Rated impulse withst<strong>and</strong> voltage of aux. circuit (kV), Uimp 4 4 4 4 4 4 4 4<br />

Typical opening time msec 40 4040 40404040 40<br />

Typical closing time msec 60 6060 60606060 60<br />

Utilization category B B B B B B B B<br />

Suitability for isolation ü ü ü ü ü ü ü ü<br />

�ixed ü ü ü ü<br />

Versions<br />

Dimensions(mm)<br />

1/4<br />

TECHNICAL DATA<br />

Drawout ü ü ü ü ü ü ü<br />

Manual ü ü ü ü ü ü ü ü<br />

<strong>Electrical</strong> ü ü ü ü ü ü<br />

CT taps for Thermo-Magnetic (DN1), Solid State (SR15, SR15G) Releases Amps 1250,1600 1000,1250,1600,2000 2000,2500<br />

CT taps for Microprocessor based (SR21, SR21E & SR61C) Releases Amps --- 1600 --- 2000 2500<br />

<strong>Electrical</strong> & Mechanical life (Operating Cycles)** 20,000 20,000 20,000 20,000 20,000 20,000 20,000 20,000<br />

Fixed<br />

D<br />

H 394 385 394 394<br />

3 pole 378 378 534 534<br />

W<br />

4 pole<br />

NA<br />

466<br />

NA<br />

NA 680<br />

NA<br />

680<br />

NA<br />

H<br />

D 431 447 431 431<br />

Drawout<br />

D<br />

H 468 468 468 468 468 468 468<br />

H<br />

W<br />

3pole<br />

4 pole<br />

399<br />

NA<br />

399<br />

487<br />

399<br />

487<br />

NA<br />

555<br />

701<br />

555<br />

701<br />

555<br />

701<br />

555<br />

701<br />

D 587 587 587 587 587 587 587<br />

NA - Not Available<br />

* Please consult us for applications at higher operational voltages upto 1000V <strong>and</strong> dc voltages.<br />

** <strong>Electrical</strong> life = Mechanical life, however arcing contacts need to be replaced depending upon wear.<br />

Arcing contacts are readily available as spares & easily replaceable at site.<br />

▲ Available in CN-CS version also.<br />

Note:1) A Choice of straight horizontal rear, straight vertical rear, flat rear <strong>and</strong> front terminal orientations in all drawout ACBs.<br />

2) Data of Icw rating for 3 sec is available on request.