AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3<br />

3/11<br />

Conformance to IS 13947 (Part 3) <strong>and</strong> IEC:60947-3<br />

Type Designation �N315 �N400 �N630<br />

No. of poles 3+Neutral 3+Neutral 3+Neutral<br />

Neutral Isolable Isolable Isolable<br />

Service temperature °C -20 to 50 -20 to 50 -20 to 50<br />

Rated operational voltage (Ue) V 415 415 415<br />

Rated insulation voltage (Ui) V 690 690 690<br />

Rated impulse withst<strong>and</strong> voltage(Uimp) kV 888<br />

Rated frequency Hz 50-60 50-60 50-60<br />

Conventional Enclosed thermal current at 40°C A 315 400 630<br />

Rated operational current Ie A<br />

AC 20A utilization category 315 400 630<br />

AC-21A utilization category 315 400 630<br />

AC-22A utilization category 315 400 630<br />

AC-23A utilization category 315 400 630<br />

DC rating at 220V DC 315 400 630<br />

No.of poles in series,utilization category<br />

TECHNICAL DATA<br />

SWITCH DISCONNECTOR �USE �OR BS TYPE �USES<br />

at rated current 2,DC22A 2,DC22A 2,DC22A<br />

Rated making capacity (436V, cosØ-0.35) A 3150 4000 6300<br />

Rated breaking capacity (436V, cosØ-0.35) A 2520 3200 5040<br />

Rated fused short circuit current kA 80 80 80<br />

with L&T fuses rating,A /Type Size 315,HQ,B4 400,HQ,B4 630,HQ,C2<br />

Capacitor duty - 415 V 50-60Hz kVAR 145 175 270<br />

Mechanical life (operating cycles) 10000 10000 10000<br />

Terminal capacity (main) mm 2 400 2x400 2x625<br />

Terminal capacity (neutral) mm 2 120 240 400<br />

Terminal screw mm M10x30 M12x40 M16x50