PROTECTION<br />

THERMO-MAGNETIC<br />

CHARACTERISTICS<br />

I-t Characteristics for DN1 Release<br />

Note :<br />

�or exact values of magnetic thershold refer overcurrent release table.<br />

Thermal Characteristics shown above are for dial setting of 1.0 in DN1 overcurrent release.<br />

SALIENT �EATURES O� THERMO MAGNETIC OVERCURRENT<br />

RELEASE TYPE DN1<br />

• Comprehensive protection - Long Time & Short Time.<br />

• Sensing through Current transformers.<br />

• Wide range of overload <strong>and</strong> short circuit setting possible with<br />

multi-tap CTs.<br />

• True RMS sensing.<br />

• Each phase can be individually adjusted for overload <strong>and</strong> short<br />

circuit settings.<br />

• Ambient temperature compensated from -50C to + 500C. • Suitable for 50/60Hz systems.<br />

• Mechanical trip test facility available.<br />

Overload Protection<br />

• Provided by bi-metals.<br />

• Continuously adjustable dial settings from 75% to 100% of CT<br />

tap.<br />

• Inverse time characteristics on overload.<br />

Short Circuit Protection<br />

• Provided by electromagnets.<br />

• Multiple settings available.<br />

• �ixed minimum impulsion time of 25 ms on short circuit by means<br />

of a flywheel to prevent tripping due to transients.<br />