10.12.2012 Views

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

✦ Easy Setting through front panel DIP Switches.<br />

✦ Indication for Power ON <strong>and</strong> trip status.<br />

✦ Test feature - helps maintenance.<br />

✦ Compact, Light weight helps in reducing panel size & thickness.<br />

TECHNICAL DATA<br />

CURRENT SENSING RELAYS<br />

Single Phase Over current / Earth fault Relay<br />

Sensitive E/� Relay <strong>and</strong> Instantaneous Current Relay<br />

Model MC11A ME11A SC14S<br />

Description 1 Ph O/C or E/� 1 Ph Sensitive E/� Instantaneous current relay<br />

Device Code 50/51 or 50N/51N 50N/51N 87 N / 64 R<br />

Design Microcontroller BasedMicrocontroller BasedStatic<br />

�unctions Available Lowset O/C -ls Lowset S E/� -ls<br />

Highset O/C -lhs<br />

Lowset E/� -Os<br />

Highset E/� -ls<br />

Highset S E/� -lhs<br />

Settings O/C ls = 50-200% Step 10% OR S E/� = 1-16% step 1%<br />

E/� ls = 10-40% Step 2% OR HS S E/� = (2-16) xls ls = 10-40% step 5%<br />

E/� ls = 20-80% Step 4%<br />

HS O/C = (2-16) xls step 2 ls<br />

HS E/� = (2-16) xls step 2 ls<br />

in steps of 2 ls OR 20-80% step 10%<br />

Time Characteristics available- Time Characteristics available- Time Characteristics available-<br />

NI, VI, EI, or Definite Time NI, VI, EI, or Definite Time Instantaneous (25ms) OR<br />

3 ranges of def Time (1, 10, 100) 3 ranges of def Time (1, 10, 100) time delayed 100ms / 200 ms<br />

TMS : 0.1 - 1.6 Step 0.1 TMS : 0.1 - 1.6 Step 0.1 Self Powered<br />

Other �eatures Site selectable Trip time Char. Site selectable Trip time Char. Relay testing Possible by ext.24V Supply<br />

Highset can be disabled Highset can be disabled<br />

Harmonic rejection<br />

�lag indication / LED indication<br />

Burden on CT 0.25 VA on CT 0.25 VA on CT 6 VA<br />

Burden on PT Not applicable Not applicable Not applicable<br />

Operating temp 0° to 55° C 0° to 55° C 0° to 55° C<br />

Weight < 1.5kg < 1.5kg < 1.5kg<br />

Burden on Auxiliary supply 5.5 VA 5.5 VA Not applicable<br />

Output Contact 2 C/O Contacts (S/R) 2 C/O Contacts (S/R) 2 C/O Contacts (S/R)<br />

Construction Drawout Drawout Drawout<br />

Dim W x H x D in mm 71 x 158 x 224 71 x 158 x 224 71 x 158 x 224<br />

Panel Cutout 62 x 142 62 x 142 62 x 142<br />

5/5<br />