Sr.No.<br />

SELECTION CHART �OR DOL STARTERS<br />

ML Relays <strong>and</strong> ML Contactors<br />

(Type “C” Co-ordination IS8544 (Part1)/IEC 292-1, Type “2” Co-ordination IS13947(Part4/Sec1)/IEC 60947-4-1)<br />

Motor 240V - 1 Phase<br />

HP kW In,A<br />

Motor Rating 415V - 3 Phase<br />

H.P. kW In,A<br />

Relay Range Contactor<br />

A<br />

HRC Back-up<br />

�use<br />

Rating, A<br />

1 0.125 0.09 0.4 0.4 - 0.65 ML0 2<br />

2 0.15 0.11 0.45 0.4 - 0.65 ML0 2<br />

3 0.2 0.15 0.57 0.4 - 0.65 ML0 2<br />

4 0.25 0.19 0.7 0.6 - 1 ML0 4<br />

5 0.33 0.25 0.88 0.6 - 1 ML0 4<br />

6 0.125 0.11 0.5 0.37 1.2 1 - 1.6 ML0 6<br />

7 0.75 0.55 1.6 1.5 - 2.5 ML0 6<br />

8 0.25 0.18 2 1 0.75 1.8 1.5 - 2.5 ML0 6<br />

9 1.25 0.92 2.1 1.5 - 2.5 ML0 8<br />

10 0.5 0.4 3.6 1.5 1.1 2.6 2.5 - 4 ML0 10<br />

11 1.75 1.3 3 2.5 - 4 ML0 10<br />

12 2 1.5 3.5 2.5 - 4 ML0 10<br />

13 0.75 0.55 2.5 1.8 4.8 4.5 - 6.5 ML0 16<br />

14 3 2.2 5 4.5 - 6.5 ML0 16<br />

15 4 3 6.2 4.5 - 6.5 ML0 16<br />

16 1 0.75 7.5 5 3.7 7.5 6 - 10 ML0 20<br />

17 1.25 0.9 8 6 4.5 9 6 - 10 ML0 25<br />

18 2 1.5 9.5 7.5 5.5 11 10 - 16 ML0 25<br />

19 3 2.25 14 10 7.5 14 10 - 16 ML1 32<br />

20 12.5 9.3 18 13 - 21 ML1.5 50<br />

21 15 11 21 20 - 32 ML1.5 63<br />

22 17.5 13 24 20 - 32 ML2 63<br />

23 20 15 28 20 - 32 ML2 63<br />

24 25 18.6 35 28 - 42 ML3 80<br />

25 30 22.5 40 28 - 42 ML3 80<br />