TECHNICAL DATA<br />

VOLTAGE / �REQUENCY RELAYS, DIRECTIONAL O/C, E/� RELAY<br />

3 Phase voltage / frequency <strong>and</strong> Load shedding Relay<br />

3 Phase voltage / frequency <strong>and</strong> zero sequence voltage Relay<br />

✦ Display of various parameters, trip count & trip data on 8 digit alphanumeric display.<br />

✦ Separate LEDs for various fault indication.<br />

✦ �our user programmable output relays.<br />

✦ Built in self supervision & self testing feature help maintenance.<br />

✦ Easy operation by 5 push buttons.<br />

✦ RS 485 port for serial communication with “MSCOM” User friendly software.<br />

Model U�D34 UM30A DM30<br />

Description 3 Ph Voltage & �req. Relay 3 Ph Voltage & �req. Relay 3 Ph Dir O/C & E/� + Highset<br />

Device Code 81, 27, 59, df/dt, de/dt 81, 27, 59, V/Hz, 59d, 59s, 59Uo 50/67 RYBN, 50 LBB<br />

Design Numeric Numeric Numeric<br />

�unctions Available �requency-4 stages selectable Over exitation-2 stages Low Set Dir O/C<br />

as under or over or under/over �requency-2 stages selectable Highset Dir O/C<br />

Voltages - 2 stages selectable as under or over or under/over Low Set Dir E/�<br />

Rate of change of frequency Voltages - 2 stages selectable Trip time Char : NI, VI, EI, Def time<br />

protection df / dt - 2 Stages as under or over CB �ailure �unction<br />

Blocking function Zero Sequence - 2 Stages MTA Setting = 0-359°<br />

Blocking function 1A or 5A site selectable<br />

Rating 100 - 125V PT input 100 - 125V PT input 100 - 125V PT input<br />

Other �eatures Display of Parameters Display of Parameters Display of Parameters<br />

Built in Self supervision Built in Self supervision Built in Self supervision<br />

RS485 Port communication RS485 Port communication RS485 Port communication<br />

Burden on CT Not applicable Not applicable 0.2 VA for 5A, 0.01 VA for 1A<br />

Burden on PT 0.04 VA 0.04 VA 8.5 VA<br />

Operating temp 10° to 60° C 10° to 60° C 10° to 60° C<br />

Weight < 2kg < 2kg < 2kg<br />

Burden on Auxiliary supply 8.5 VA 8.5 VA 0.04 VA<br />

Output Contacts 4 C/O, S/R or H/R or Time del 4 C/O, S/R or H/R or Time del 4 C/O, S/R or H/R or Time del<br />

1 C/O for self supervision 1 C/O for self supervision 1 C/O for self supervision<br />

Construction Drawout Drawout Drawout<br />

Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224<br />

Panel Cutout 113 x 142 113 x 142 113 x 142