Limiter for MG 1<br />

Rated short-circuit breaking capacity when connected in series with MG1<br />

upto AC 415V kA kA 50<br />

Rated operational voltage, Ue V 415<br />

Rated frequency Hz 50/60<br />

Max. rated current, ln<br />

St<strong>and</strong> alone upto 30°C A 63<br />

St<strong>and</strong> alone upto 55°C A 56<br />

Adjacent upto 30°C A 56<br />

Adjacent upto 55°C A 50<br />

Mechanical endurance op. Cyls 100 000<br />

Auxiliary contacts<br />

Rated operational current, le 230V A 3 3<br />

400V A 1.5 1.5<br />

500V A 1 1<br />

Utilization category AC - 15<br />

Terminal Capacity, Solid or Str<strong>and</strong>ed mm 2 1 x 0.5 to 2 x 2.5<br />

Under voltage release<br />

Power consumption pickup VA / W 10/6<br />

holdon VA / W 4.2/2<br />

Tripping voltage tripping V 0.7 to 0.35 x Us<br />

pickup V 0.85 to 1.1 x Us<br />

Max. opening time ms 20<br />

Shunt trip<br />

St<strong>and</strong>ards<br />

ACCESSORIES<br />

IEC 947-1; IEC 947-2; IEC 947-4-1<br />

MG1<br />

MG2<br />

Power consumption during pickup VA / W 10/6 65/57<br />

Max. permissible comm<strong>and</strong> duration S - 5<br />

Tripping voltage V 0.7 to 1.1 x Us 0.7 to 1.1 x Us<br />

Max. opening time ms 20 20<br />

11/6<br />