2<br />

2/9<br />

TECHNICAL DATA - DS<br />

Type Designation DS 100 DS 125 DS 160<br />

Rated Uninterrupted current<br />

at 40 o C. - Ith (AC/DC) A 100 125 160<br />

Rated impulse withst<strong>and</strong> voltage - Uimp kV 8 8 8<br />

Rated operational voltage - Ue V AC 415 415 415<br />

V DC 250 250 250<br />

�requency Hz 50/60 50/60 50/60<br />

Rated insulation voltage - Ui V 690 690 690<br />

Operating Temperature °C -5 to +55 -5 to +55 -5 to +55<br />

Overvoltage category / pollution degree III/3 III/3 III/3<br />

Rated Short-circuit making capacity - Icm kA 17 17 32<br />

Rated ultimate S.C. breaking capacity - Icu<br />

at 415V ac kA 10 10 16<br />

Rated Service S.C. breaking capacity - Ics<br />

at 415V ac kA 50% 50% 50%<br />

Utilisation category A A A<br />

Mechanical life<br />

<strong>Electrical</strong> life<br />

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic<br />

Overload release setting �ixed �ixed �ixed<br />

Short Circuit release setting (+/- 20%) 9*In 9*In 8*In<br />

Weight kg 1.7 1.7 1.7<br />

Terminal capacity Cables mm 2 50 70 95<br />

Accessories<br />

As per st<strong>and</strong>ard IS 13947-2 / IEC 60947-2<br />

Links mm 16 22 22<br />

Auxiliary contacts (1NO+1NC) (1NO+1NC) (1NO+1NC)<br />

Shunt release y y y<br />

Under voltage release y y y<br />

Trip alarm contacts y y y<br />

Earth fault module y y y<br />

Rotary operating mechanism y y y