10.12.2012 Views

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

1 Rating (A) 400 630 800<br />

Type Designation CN-CS CN-CS CN-CS..E CN-CS..E S C H<br />

Rated Current (A) 400C In 400 630 630 800 800 800 800<br />

Rated Operational Voltage (V) 50/60Hz Ue* 415 415 415 415 415 415 415<br />

Rated insulation voltage (V), 50/60Hz Ui 690 690 690 690 1000 1000 1000<br />

No. of poles 3 3 3 3 3 3/4 3/4<br />

Rated ultimate short circuit Icu<br />

breaking capacity<br />

50/60Hz (kA rms)<br />

380/415/500V 36.6 36.6 25 36.6 50 50 65<br />

Rated service short circuit Ics<br />

breaking capcity<br />

50/60Hz (kA rms)<br />

380/415/500V 36.6 36.6 25 36.6 38 50 65<br />

Rated short time withst<strong>and</strong> capacity Icw 0.5sec 36.6 36.6 25 36.6 38 50 65<br />

50/60Hz (kA rms) 1sec 25 25 25 25 38 50 65<br />

Rated making capacity Icm<br />

50/60Hz (kA peak) 380/415/500V 77 77 52.5 77 105 105 143<br />

Rated impulse withst<strong>and</strong> voltage of main circuit (kV), Uimp 8 8 8 8 8 8 8<br />

Rated impulse withst<strong>and</strong> voltage of aux. circuit (kV), Uimp 4 4 4 4 4 4 4<br />

Typical opening time msec 4040404040 4040<br />

Typical closing time msec 6060606060 6060<br />

Utilization category B B B B B B B<br />

Suitability for isolation ü ü ü ü ü ü ü<br />

�ixed ü ü ü ü ü▲<br />

Versions<br />

Dimensions(mm)<br />

1/2<br />

TECHNICAL DATA<br />

Drawout ü ü ü<br />

Manual ü ü ü ü ü ü ü<br />

<strong>Electrical</strong> ü ü<br />

CT taps for Thermo-Magnetic (DN1), Solid State (SR15, SR15G) Releases Amps 320,400 400,500,630 400,500,640,800<br />

CT taps for Microprocessor based (SR21, SR21E & SR61C) Releases Amps --- --- --- --- 800<br />

<strong>Electrical</strong> & Mechanical life (Operating Cycles)** 15,000 15,000 15,000 20,000 20,000 20,000<br />

Fixed D<br />

H 385 385 385 385 394<br />

3 pole 331.2 331.2 331.2 331.2<br />

378<br />

H<br />

W<br />

4 pole NA NA NA NA<br />

NA<br />

466<br />

NA<br />

D 447 447 447 447 431<br />

Drawout<br />

D<br />

H 468 468 468<br />

H<br />

W<br />

3pole<br />

4 pole<br />

NA<br />

399<br />

NA<br />

399<br />

487<br />

399<br />

487<br />

D 587 587 587<br />

NA - Not Available<br />

* Please consult us for applications at higher operational voltages upto 1000V <strong>and</strong> dc voltages.<br />

** <strong>Electrical</strong> life = Mechanical life, however arcing contacts need to be replaced depending upon wear.<br />

Arcing contacts are readily available as spares & easily replaceable at site.<br />

▲ Available in CN-CS version also.<br />

Note:1) CN-CS400, CN-CS630, 630E, 800E & 1000E ACB are available only with DN1 release.<br />

2) A Choice of straight horizontal rear, straight vertical rear, flat rear <strong>and</strong> front terminal orientations in all drawout ACBs.<br />

3) Data of Icw rating for 3 sec is available on request.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!