2<br />

2/13<br />

TECHNICAL DATA - DH<br />

Type Designation DH 100 DH 125 DH 160 DH 200<br />

Rated Uninterrupted current<br />

at 40o C. - Ith (AC/DC) A 100 125 160 200<br />

Rated impulse withst<strong>and</strong> voltage - Uimp kV 8 8 8 8<br />

Rated operational voltage - Ue V 415 415 415 415<br />

V DC 250 250 250 250<br />

�requency Hz 50/60 50/60 50/60 50/60<br />

Rated insulation voltage - Ui V 690 690 690 690<br />

Operating Temperature °C -5 to +55 -5 to +55 -5 to +55 -5 to +55<br />

Overvoltage category / pollution degree III/3 III/3 III/3 III/3<br />

Rated Short-circuit making capacity - Icm kA 52.5 73.5 73.5 73.5<br />

Rated ultimate S.C. breaking capacity - Icu<br />

at 660V ac kA 5 7 7 7<br />

at 550V ac kA 12 18 18 18<br />

at 500V ac kA 18 25 25 25<br />

at 415V ac kA 25 35 35 35<br />

at 380V ac kA 25 35 35 35<br />

at 240V ac kA 50 60 60 60<br />

Rated Service S.C. breaking capacity - Ics<br />

at 415V ac kA 100% 75% 75% 50%<br />

DC Breaking capacity at 250 V, L/R