TECHNICAL DATA - DTH 800 INST.<br />

Type Designation DTH 800 INST.<br />

Rated Uninterrupted current<br />

at 40o C. - Ith (AC/DC) A 800<br />

Rated impulse withst<strong>and</strong> voltage - Uimp kV 8<br />

Rated operational voltage - Ue V 415<br />

�requency Hz 50/60<br />

Rated insulation voltage - Ui V 600<br />

Operating Temperature °C -5 to +55<br />

Overvoltage category / pollution degree III/3<br />

Rated ultimate S.C. breaking capacity - Icu<br />

at 415V ac kA 50<br />

Rated Service S.C. breaking capacity - Ics<br />

at 415V ac (of Icu) kA 50%<br />

Utilisation category A<br />

Mechanical life Ops. 8000<br />

<strong>Electrical</strong> life Ops. 1200<br />

Release Type Magnetic<br />

Short Circuit release setting (+/- 20%) 360A, 550A, 850A, 1050A<br />

Weight kg 10<br />

Terminal capacity Cables mm 2 2*240<br />

Accessories<br />

Links mm 40 (Max. 15 thk.)<br />

Auxiliary contacts y<br />

Shunt release y<br />

Under voltage release y<br />

Trip alarm contacts y<br />

Earth fault module y<br />

Rotary operating mechanism y<br />

2/24<br />