AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

AIR CIRCUIT BREAKERS - Electrical and Electronics Division

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

1<br />

1/8<br />

Type of<br />

Protection<br />

PROTECTION<br />

COMPUTER COMPATIBLE & COMMUNICATION CAPABLE<br />

SALIENT �EATURES O� RELEASE TYPE SR61C<br />

✦ Display of rms currents (Phase, Highest among phases) <strong>and</strong> Trip data by 4-seven<br />

segment LEDs.<br />

✦ Non-volatile memory for Storage <strong>and</strong> display of trip history for last 5 tripping<br />

operations.<br />

✦ Communication with PC <strong>and</strong> breaker control through RS485 port.<br />

✦ Serial communication by MODBUS-RTU protocol.<br />

✦ Separate indication for Power-ON <strong>and</strong> Programming mode or fault.<br />

✦ Individual fault indication by LEDs. LED indication can be reset by the Reset button<br />

on the release. However, resetting is not possible when fault is present.<br />

✦ Direct tripping of breaker - Reliable <strong>and</strong> Minimum tripping time.<br />

✦ Blocking function to inhibit any of the trip functions to achieve intelligent<br />

discrimination.<br />

✦ Protection against failure of breaker to trip within set time delay (Range : 0.05 s to<br />

0.25 s in steps of 0.01 s)<br />

✦ Automatic doubling feature to prevent nuisance tripping during motor starting. Can<br />

be Enabled or Disabled.<br />

✦ Protection settings can be changed through computer while breaker is carrying<br />

current.<br />

✦ 5 Output relays<br />

R1 Used for trip output (Can be programmed in manual or auto reset mode)<br />

R2 �or Instantaneous output<br />

R3 �or opening the breaker<br />

R4 �or closing the breaker<br />

R5 �or indication of internal error / program error / auxiliary supply failure<br />

✦ Auxiliary power supply required : 110V to 240V ac/dc +10%<br />

Auxiliary power supply burden < 10 VA<br />

Setting Ranges<br />

Pick-up current Time Delay<br />

Ir-0.5 to 1.0 times In 2 to 30 sec. at 6 times Ir<br />

Long Time Steps : 0.50, 0.55, 0.60, 0.65, 0.70, 0.75,<br />

0.80, 0.85, 0.9, 0.95, 1.00<br />

Steps : 2, 10, 20, 30 sec<br />

2 to 16 times In Inst. to 400 ms<br />

Short Time Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16 Steps : Inst., 100, 200, 300, 400 ms<br />

0.2 to 0.6 times In 100 to 400 ms<br />

Ground �ault Steps : 0.2, 0.3, 0.4, 0.5, 0.6 Steps : 100, 200, 300, 400 ms & Disable