TECHNICAL DATA - DX..H (3/4 POLE)<br />

Type Designation DX 100H DX 125H DX 160H DX 200H<br />

Rated Uninterrupted current<br />

at 40 ° C. - Ith (AC/DC) A 100 125 160 200<br />

Rated impulse withst<strong>and</strong> voltage - Uimp kV 8 8 8 8<br />

Rated operational voltage - Ue V 415 415 415 415<br />

V DC 440 440 440 440<br />

�requency Hz 50/60 50/60 50/60 50/60<br />

Rated insulation voltage - Ui V 690 690 690 690<br />

Operating Temperature °C -5 to +55 -5 to +55 -5 to +55 -5 to +55<br />

Overvoltage category / pollution degree III/3 III/3 III/3 III/3<br />

Rated Short-circuit making capacity - Icm kA 220 550 220 220<br />

Rated ultimate S.C. breaking capacity - Icu<br />

at 690V ac kA 8 8 8 8<br />

at 500V ac kA 20 20 20 20<br />

at 415V ac kA 65 65 65 65<br />

at 230V ac<br />

Rated Service S.C.<br />

kA 100 100 100 100<br />

breaking capacity - Ics (of Icu) kA 75% 75% 75% 75%<br />

DC Breaking capacity at 440 V kA 25 25 25 25<br />

Utilisation category A A A A<br />

Rated short-time withst<strong>and</strong> current Icw (1 Sec) kA - - - -<br />

Mechanical life Ops. 20000 20000 20000 20000<br />

<strong>Electrical</strong> life (AC3, 400V) Ops. 6000 6000 6000 3500<br />

Release Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic<br />

Overload release setting 80-100% 80-100% 80-100% 80-100%<br />

Short Circuit release setting 6-12*In 6-12*In 6-12*In 6-12*In<br />

Mechanical Shock resistance g 20 20 20 20<br />

Weight (3 - Pole) kg 1.7 1.7 1.7 1.7<br />

(4 - Pole)<br />

Accessories<br />

kg 1.7 1.7 1.7 1.7<br />

Auxiliary contacts y y y y<br />

Shunt release y y y y<br />

Under voltage release y y y y<br />

Trip indicating auxiliary contacts y y y y<br />

Earth fault module y y y y<br />

Rotary operating mechanism y y y y<br />

Residual-current protection module y y y y<br />

Remote operator y y y y<br />

Withdrawable unit - - - -<br />

Plug-in module y y y y<br />

Mechanical interlock y y y y<br />

Paralleling mechanism<br />

Load monitoring<br />

y y y y<br />

2/20<br />