2<br />

2/21<br />

TECHNICAL DATA - DX..H (3/4 POLE)<br />

Type Designation DX 250H DX 400H DX 630H DX 800H<br />

Rated Uninterrupted current<br />

at 40 ° C. - Ith (AC/DC) A 250 400 630 800<br />

Rated impulse withst<strong>and</strong> voltage - Uimp kV 8 8 8 8<br />

Rated operational voltage - Ue V 415 415 415 415<br />

V DC 440 – – –<br />

�requency Hz 50/60 50/60 50/60 50/60<br />

Rated insulation voltage - Ui V 690 690 690 690<br />

Operating Temperature °C -5 to +55 -5 to +55 -5 to +55 -5 to +55<br />

Overvoltage category / pollution degree III/3 III/3 III/3 III/3<br />

Rated Short-circuit making capacity - Icm kA 220 440 440 275<br />

Rated ultimate S.C. breaking capacity - Icu<br />

at 690V ac kA 8 30 30 25<br />

at 500V ac kA 20 65 65 45<br />

at 415V ac kA 65 100 100 65<br />

at 230V ac<br />

Rated Service S.C.<br />

kA 100 200 200 100<br />

breaking capacity - Ics (of Icu) kA 75% 50% 50% 75%<br />

DC Breaking capacity at 440 V kA 25 - - -<br />

Utilisation category A A / B A B<br />

Rated short-time withst<strong>and</strong> current Icw (1 Sec) kA - 8 8 15 (0.3 S)<br />

Mechanical life Ops. 20000 20000 20000 2500<br />

<strong>Electrical</strong> life (AC3, 400V) Ops. 3500 5000 5000 500 (AC1)<br />

Release Type Thermal-Magnetic Electronic Electronic Electronic<br />

Overload release setting 80-100% 50-100% 50-100% 50-100%<br />

Short Circuit release setting 6-12*In 2-12*In 2-12*In 2-12*In<br />

Mechanical Shock resistance g 20 20 20 20<br />

Weight (3 - Pole) kg 1.7 9.1 9.1 20.4<br />

(4 - Pole)<br />

Accessories<br />

kg 1.7 11.9 11.9 26.4<br />

Auxiliary contacts y y y y<br />

Shunt release y y y y<br />

Under voltage release y y y y<br />

Trip indicating auxiliary contacts y y y y<br />

Earth fault module y y y y<br />

Rotary operating mechanism y y y y<br />

Residual-current protection module y y y -<br />

Remote operator y y y y<br />

Withdrawable unit - y y y<br />

Mechanical interlock y y y y<br />

Paralleling mechanism y y y -<br />

Load monitoring y