More detailed descripti<strong>on</strong> <strong>and</strong> input data are given in HVCA publicati<strong>on</strong> DW<br />

171 [21] <strong>and</strong> CIBSE guide B [11] .<br />

4. Air Changes Method: A per hour vent rate equivalent to 40 times <strong>the</strong> ventilati<strong>on</strong><br />

volume is c<strong>on</strong>sidered minimum for comfort under normal c<strong>on</strong>diti<strong>on</strong>s, but rates as<br />

high as 60-100 volumes per hour may be required where high-output equipment<br />

is densely located. Using this method air will may be extracted via both a hood<br />

extract <strong>and</strong> a ceiling extract.<br />

5. Linear Extract Method: Each linear meter <strong>of</strong> active filter length is assigned a<br />

vent rate depending <strong>on</strong> <strong>the</strong> vent canopy type.<br />

6. Meals Method: Extract rate in litres/sec is expressed as 10-15 times <strong>the</strong> number<br />

<strong>of</strong> meals served per hour.<br />

7. Area Method: Area <strong>of</strong> <strong>the</strong> cooking space in m 2 is multiplied by 15-20 litres/sec to<br />

give an approximate volume flow rate.<br />

Table 4.1 Recommended Canopy Types<br />

Canopy type<br />

(see figure 4.3)<br />

Light duty Medium duty Heavy duty Extra heavy duty<br />

Wall mounted 0.23-0.31 (m 3 /s) 0.31-0.46<br />

(m 3 /s)<br />

Single Isl<strong>and</strong> 0.39-0.46 (m 3 /s) 0.46-0.62<br />

(m 3 /s)<br />

Double Isl<strong>and</strong> 0.23-0.31 (m 3 /s) 0.31-0.46<br />

(m 3 /s)<br />

Eyebrow 0.23-0.39 (m 3 /s) 0.23-0.39<br />

(m 3 /s)<br />

Passover/Backs<br />

helf<br />

4.2.3 Make-up air<br />

0.15-0.31 (m 3 /s) 0.31-0.46<br />

(m 3 /s)<br />

39<br />

0.31-0.62 (m 3 /s) >0.54 (m 3 /s)<br />

0.46-0.93 (m 3 /s) >0.85 (m 3 /s)<br />

0.39-0.62 (m 3 /s) >0.77 (m 3 /s)<br />

-- --<br />

0.46-0.62 (m 3 /s) not<br />

recommended<br />

In order for a kitchen extract system to functi<strong>on</strong> correctly <strong>the</strong> overall design must<br />

include provisi<strong>on</strong> for make-up or replacement air. Air can be made up ei<strong>the</strong>r by<br />

natural infiltrati<strong>on</strong> or by using a mechanical supply. If a mechanical input system is<br />

used, typically 85% <strong>of</strong> air will be provided mechanically <strong>and</strong> <strong>the</strong> remaining 15% by<br />

natural means.<br />

The Food Safety (General Food Hygiene) Regulati<strong>on</strong>s 1995 [20] require that<br />

‘mechanical air flow <strong>from</strong> a c<strong>on</strong>taminated area to a clean area must be avoided’.<br />

Mechanical systems <strong>of</strong>fer a greater degree <strong>of</strong> c<strong>on</strong>trol <strong>and</strong> avoid:<br />

• Unfiltered air entering <strong>the</strong> kitchen;