More detailed descripti<strong>on</strong> <strong>and</strong> input data are given in HVCA publicati<strong>on</strong> DW<br />
171 [21] <strong>and</strong> CIBSE guide B [11] .<br />
4. Air Changes Method: A per hour vent rate equivalent to 40 times <strong>the</strong> ventilati<strong>on</strong><br />
volume is c<strong>on</strong>sidered minimum for comfort under normal c<strong>on</strong>diti<strong>on</strong>s, but rates as<br />
high as 60-100 volumes per hour may be required where high-output equipment<br />
is densely located. Using this method air will may be extracted via both a hood<br />
extract <strong>and</strong> a ceiling extract.<br />
5. Linear Extract Method: Each linear meter <strong>of</strong> active filter length is assigned a<br />
vent rate depending <strong>on</strong> <strong>the</strong> vent canopy type.<br />
6. Meals Method: Extract rate in litres/sec is expressed as 10-15 times <strong>the</strong> number<br />
<strong>of</strong> meals served per hour.<br />
7. Area Method: Area <strong>of</strong> <strong>the</strong> cooking space in m 2 is multiplied by 15-20 litres/sec to<br />
give an approximate volume flow rate.<br />
Table 4.1 Recommended Canopy Types<br />
Canopy type<br />
(see figure 4.3)<br />
Light duty Medium duty Heavy duty Extra heavy duty<br />
Wall mounted 0.23-0.31 (m 3 /s) 0.31-0.46<br />
(m 3 /s)<br />
Single Isl<strong>and</strong> 0.39-0.46 (m 3 /s) 0.46-0.62<br />
(m 3 /s)<br />
Double Isl<strong>and</strong> 0.23-0.31 (m 3 /s) 0.31-0.46<br />
(m 3 /s)<br />
Eyebrow 0.23-0.39 (m 3 /s) 0.23-0.39<br />
(m 3 /s)<br />
Passover/Backs<br />
helf<br />
4.2.3 Make-up air<br />
0.15-0.31 (m 3 /s) 0.31-0.46<br />
(m 3 /s)<br />
39<br />
0.31-0.62 (m 3 /s) >0.54 (m 3 /s)<br />
0.46-0.93 (m 3 /s) >0.85 (m 3 /s)<br />
0.39-0.62 (m 3 /s) >0.77 (m 3 /s)<br />
-- --<br />
0.46-0.62 (m 3 /s) not<br />
recommended<br />
In order for a kitchen extract system to functi<strong>on</strong> correctly <strong>the</strong> overall design must<br />
include provisi<strong>on</strong> for make-up or replacement air. Air can be made up ei<strong>the</strong>r by<br />
natural infiltrati<strong>on</strong> or by using a mechanical supply. If a mechanical input system is<br />
used, typically 85% <strong>of</strong> air will be provided mechanically <strong>and</strong> <strong>the</strong> remaining 15% by<br />
natural means.<br />
The Food Safety (General Food Hygiene) Regulati<strong>on</strong>s 1995 [20] require that<br />
‘mechanical air flow <strong>from</strong> a c<strong>on</strong>taminated area to a clean area must be avoided’.<br />
Mechanical systems <strong>of</strong>fer a greater degree <strong>of</strong> c<strong>on</strong>trol <strong>and</strong> avoid:<br />
• Unfiltered air entering <strong>the</strong> kitchen;