Table 4.3 – <strong>Noise</strong> characteristics <strong>of</strong> different fan types<br />

Fan Type <strong>Noise</strong> Descripti<strong>on</strong><br />

Centrifugal Lower<br />

frequencies<br />

Axial Mid–range<br />

frequencies<br />

Mixed flow Lower<br />

frequencies<br />

Air enters axially <strong>and</strong> is discharged radially.<br />

Air enters <strong>and</strong> leaves <strong>the</strong> fan in a straight–through<br />

c<strong>on</strong>figurati<strong>on</strong>.<br />

The air path is intermediate between axial <strong>and</strong> centrifugal.<br />

Cross flow Varied L<strong>on</strong>g cylindrical impeller with a large number <strong>of</strong> shallow<br />

blades discharging via a l<strong>on</strong>g slot.<br />

Propeller T<strong>on</strong>al peaks Similar to an axial fan, but mounted in a ring permitting<br />

both radial <strong>and</strong> axial discharge, higher volume <strong>and</strong> lower<br />

pressure.<br />

4.6 Access Panels For Cleaning<br />

Access panels should be suitable for <strong>the</strong> purpose for which <strong>the</strong>y are intended. They<br />

should incorporate quick release catches, sealing gasket <strong>and</strong> <strong>the</strong>rmal, acoustic <strong>and</strong><br />

fire-rated insulati<strong>on</strong> properties equal to that <strong>of</strong> <strong>the</strong> duct to which <strong>the</strong> panel is fitted.<br />

The panel <strong>and</strong> aperture should be free <strong>of</strong> any sharp edges. <str<strong>on</strong>g>Guidance</str<strong>on</strong>g> <strong>on</strong> <strong>the</strong> required<br />

locati<strong>on</strong>s for access panels is provided in Table 4.4.<br />

Table 4.4: Locati<strong>on</strong> <strong>of</strong> access panels for cleaning<br />

Locati<strong>on</strong> <strong>of</strong> access panel Cleaning<br />

C<strong>on</strong>trol Dampers Both sides<br />

Fire Dampers One side<br />

Heating/cooling Coils Both sides<br />

Attenuators (Rectangular) Both sides<br />

Attenuators (Circular) One side<br />

Filter secti<strong>on</strong>s Both sides<br />

Air turning vanes Both sides<br />

Changes <strong>of</strong> Directi<strong>on</strong> One side<br />

In Duct Fan/Devices Both sides<br />

51