External pressure setting for tuning 5CSL0-06B<br />

Table 1<br />

[ Notes ]<br />

Static Pressure(mmAq)<br />

Model Name Step CMM<br />

ABNH186HLAD<br />

[UB18 NHD]<br />

ABNH246HLAD<br />

[UB24 NHD]<br />

ABNH306GLAD<br />

[UB30 NGD]<br />

ABNH366GLAD<br />

[UB36 NGD]<br />

ABNH426RLAD<br />

[UB42 NRD]<br />

ABNH486RLAD<br />

[UB48 NRD]<br />

ABNH606RLAD<br />

[UB60 NRD]<br />

0 2 4 6 8<br />

Setting Value<br />

10 12 14 15<br />

High 16.5 235 230 225 215 180 - - - -<br />

Med 14.5 245 238 235 230 215 - - - -<br />

Low 13 254 252 248 245 240 - - - -<br />

High 18 220 205 190 50 1 - - - -<br />

Med 16.5 235 230 220 200 100 - - - -<br />

Low 14 250 240 235 230 210 - - - -<br />

High 26.5 153 150 150 148 130 1 - - -<br />

Med 23 173 173 175 175 170 155 - - -<br />

Low 20 190 190 190 190 190 190 - - -<br />

High 32 230 230 225 220 150 1 - - -<br />

Med 29 240 238 237 235 230 220 - - -<br />

Low 26.5 245 245 243 243 240 240 - - -<br />

High 36 238 235 230 225 220 215 - - -<br />

Med 32 253 250 245 240 235 230 - - -<br />

Low 28 255 255 255 255 250 248 - - -<br />

High 40 230 225 220 215 205 200 190 180 160<br />

Med 35 250 245 240 235 230 220 215 210 200<br />

Low 30 255 255 255 250 245 240 235 230 225<br />

High 50 185 180 174 162 154 140 90 5 1<br />

Med 45 210 205 199 191 189 180 155 138 110<br />

Low 40 230 225 219 215 210 205 193 180 171<br />

1. To get the desired Airflow & ESP combination from the table set the matching value from the table. Value<br />

other than that in table will not give the combinations <strong>of</strong> airflow & ESP which are mentioned in the table.<br />

2. Table data is based at 230V. According to the fluctuation <strong>of</strong> voltage, air flow rate varies.<br />

3) Duct work must be designed within the range <strong>of</strong> on installing the unit.<br />

4) If duct work is designed under External Static Pressure adjust the External Static Pressure ap<strong>pl</strong>ying<br />

air damper.<br />

120 Duct (H)