5CSL0-06B<br />

3) Calculation <strong>of</strong> actual system capacity<br />

① Outdoor unit rated capacity<br />

Qodu(rated) [from specification table]<br />

② Outdoor unit capacity at Ti, To temperature.<br />

Qodu(Ti, To) [from capacity table]<br />

③ Outdoor unit capacity coefficient factor<br />

F(Ti, To) = Qodu(Ti, To) / Qodu(rated)<br />

④ Piping correction factor [from capacity coefficient factor table]<br />

Fmain (length, elevation) for main piping length or elevation<br />

Fbranch (length, elevation) for branch piping length or elevation<br />

⑤ Individual indoor unit combinational capacity<br />

Qidu (combi) = Qodu(rated) x Qidu(rated) / Qidu(rated-total)<br />

⑥ Individual indoor unit actual capacity<br />

Qidu (actual) = Qodu(combi) x F(Ti, To) x Fmain (length, elevation) x Fbranch (length, elevation)<br />

Exam<strong>pl</strong>e) • Outdoor unit model : AUUW126D[UU12W ULD]<br />

• Indoor units (ATNH12GRLED[UT12 NRD]) : 3.5 kW<br />

• Outdoor temperature : 40.0°CDB<br />

• Indoor temperature: 19.0°CWB<br />

• Main piping length(O/D to BD):15m<br />

• Indoor unit actual cooling capacity in A room?<br />

- Qodu(rated) : 3.40kW<br />

- Qodu(Ti, To) : 3.28 kW<br />

- F(Ti, To) : 3.28 / 3.40 = 96.47%<br />

- Fmain (length, elevation) = 99.3%<br />

- Qind(actual) =3.4kW x 0.9647 x 0.993 = 3.257kW<br />

Capacity coefficient factor<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 207