5CSL0-06B Electrical work<br />
2.5 Electrical work<br />
2.5.1 Precautions<br />
CAUTION<br />
When knocking out knock holes<br />
• To punch a knock hole, hit on it with a hammer.<br />
• After knocking out the holes, we recommend you paint<br />
the edges and areas around the edges using paint to<br />
prevent rusting.<br />
• When passing electrical wiring through the knock holes,<br />
remove any burrs from the knock holes and wrap the<br />
wiring with protective tape to prevent damage.<br />
Use a conduit for the cable<br />
• Outside the unit, make sure the thin signal cable (i.e. for the<br />
remote control, between units, etc.) and the thick electric<br />
wiring do not pass near each other and use <strong>of</strong> the shield signal<br />
cable is recommended.<br />
Otherwise, the outdoor unit may be affected by electrical<br />
noise (external noise), and malfunction or fail.<br />
• Secure the wiring with the accessory clamps so that it does<br />
not touch the piping.<br />
• Make sure the wiring and the electric parts box cover do not<br />
stick up above the structure, and close the cover firmly.<br />
CAUTION<br />
Burr<br />
If there are any possibilities that<br />
small animals or insects enter the<br />
system through the knock holes,<br />
<strong>pl</strong>ug the holes with packing<br />
materials (to be prepared onsite).<br />
Do not operate the air conditioner until the refrigerant piping<br />
work is com<strong>pl</strong>eted.<br />
(Operating the air conditioner before the refrigerant piping<br />
work is com<strong>pl</strong>eted may damage the compressor.)<br />
• Install an earth leakage circuit breaker.<br />
Since this is a inverter air conditioner. In order to prevent<br />
malfunction <strong>of</strong> the earth leakage breaker itself, use a<br />
breaker resistant to higher harmonics.<br />
• After finishing the electric work, confirm that each electric<br />
part and terminal inside the electric parts box is connected<br />
securely.<br />
NOTE<br />
• Only pr<strong>of</strong>essional electricians having sufficient knowledge<br />
should perform the electrical wiring work.<br />
Perform the electrical wiring work in accordance with the<br />
electrical wiring diagram.<br />
Make sure to set OFF the branch switch and over current<br />
breaker before starting the work.<br />
• Install an earth leakage breaker.<br />
• Perform grounding to the indoor units and outdoor units.<br />
• Do not connect the ground wire to gas pipes, sewage<br />
pipes, lightning rods telephone ground wires.<br />
• Gas pipes ···· Can ex<strong>pl</strong>ode or catch fire if gas leaks.<br />
• Sewage pipes···· Provides no grounding effect if hard<br />
<strong>pl</strong>astic pipes are used.<br />
• Telephone ground wires and lightening rods ···· dangerous<br />
when struck by lightening due to abnormal rise in the<br />
ele trical potential in the ground.<br />
• Use only copper wires.<br />
• Make sure to shut down the power before starting the electric<br />
wiring work.<br />
Do not set ON any switch until the work is com<strong>pl</strong>eted.<br />
• The outdoor unit has an inverter compresser which generates<br />
noise and charges the outer casing with the leakag<br />
current. The outdoor unit should be grounded so that the<br />
effect <strong>of</strong> the generated noise on othe equipment can be<br />
reduced, and that the outer casing can be discharged.<br />
• Never install a phase advancing capacitor for power factor<br />
improvement.<br />
(Even if it is installed, the power factor is not improved. And<br />
if it is installed, the outdoor unit is abnormally overheated.)<br />
• Use specified electric wires in the wiring, and connect them<br />
securely.<br />
Fix them in such a way that external force is not ap<strong>pl</strong>ied at<br />
the terminals<br />
(transmission wiring in the local field and ground terminal).<br />
• Never push excessive electric wires into the units.<br />
• Protect electric wires with conduit tubes or other proper<br />
tubes so that they will not be damaged by edges <strong>of</strong> knock<br />
holes.<br />
• Do not use multi conductor cable which have more than 5<br />
wires in one core.<br />
Guideline for each installation process 307