5CSL0-06B Electrical work<br />

2.5 Electrical work<br />

2.5.1 Precautions<br />

CAUTION<br />

When knocking out knock holes<br />

• To punch a knock hole, hit on it with a hammer.<br />

• After knocking out the holes, we recommend you paint<br />

the edges and areas around the edges using paint to<br />

prevent rusting.<br />

• When passing electrical wiring through the knock holes,<br />

remove any burrs from the knock holes and wrap the<br />

wiring with protective tape to prevent damage.<br />

Use a conduit for the cable<br />

• Outside the unit, make sure the thin signal cable (i.e. for the<br />

remote control, between units, etc.) and the thick electric<br />

wiring do not pass near each other and use <strong>of</strong> the shield signal<br />

cable is recommended.<br />

Otherwise, the outdoor unit may be affected by electrical<br />

noise (external noise), and malfunction or fail.<br />

• Secure the wiring with the accessory clamps so that it does<br />

not touch the piping.<br />

• Make sure the wiring and the electric parts box cover do not<br />

stick up above the structure, and close the cover firmly.<br />

CAUTION<br />

Burr<br />

If there are any possibilities that<br />

small animals or insects enter the<br />

system through the knock holes,<br />

<strong>pl</strong>ug the holes with packing<br />

materials (to be prepared onsite).<br />

Do not operate the air conditioner until the refrigerant piping<br />

work is com<strong>pl</strong>eted.<br />

(Operating the air conditioner before the refrigerant piping<br />

work is com<strong>pl</strong>eted may damage the compressor.)<br />

• Install an earth leakage circuit breaker.<br />

Since this is a inverter air conditioner. In order to prevent<br />

malfunction <strong>of</strong> the earth leakage breaker itself, use a<br />

breaker resistant to higher harmonics.<br />

• After finishing the electric work, confirm that each electric<br />

part and terminal inside the electric parts box is connected<br />

securely.<br />

NOTE<br />

• Only pr<strong>of</strong>essional electricians having sufficient knowledge<br />

should perform the electrical wiring work.<br />

Perform the electrical wiring work in accordance with the<br />

electrical wiring diagram.<br />

Make sure to set OFF the branch switch and over current<br />

breaker before starting the work.<br />

• Install an earth leakage breaker.<br />

• Perform grounding to the indoor units and outdoor units.<br />

• Do not connect the ground wire to gas pipes, sewage<br />

pipes, lightning rods telephone ground wires.<br />

• Gas pipes ···· Can ex<strong>pl</strong>ode or catch fire if gas leaks.<br />

• Sewage pipes···· Provides no grounding effect if hard<br />

<strong>pl</strong>astic pipes are used.<br />

• Telephone ground wires and lightening rods ···· dangerous<br />

when struck by lightening due to abnormal rise in the<br />

ele trical potential in the ground.<br />

• Use only copper wires.<br />

• Make sure to shut down the power before starting the electric<br />

wiring work.<br />

Do not set ON any switch until the work is com<strong>pl</strong>eted.<br />

• The outdoor unit has an inverter compresser which generates<br />

noise and charges the outer casing with the leakag<br />

current. The outdoor unit should be grounded so that the<br />

effect <strong>of</strong> the generated noise on othe equipment can be<br />

reduced, and that the outer casing can be discharged.<br />

• Never install a phase advancing capacitor for power factor<br />

improvement.<br />

(Even if it is installed, the power factor is not improved. And<br />

if it is installed, the outdoor unit is abnormally overheated.)<br />

• Use specified electric wires in the wiring, and connect them<br />

securely.<br />

Fix them in such a way that external force is not ap<strong>pl</strong>ied at<br />

the terminals<br />

(transmission wiring in the local field and ground terminal).<br />

• Never push excessive electric wires into the units.<br />

• Protect electric wires with conduit tubes or other proper<br />

tubes so that they will not be damaged by edges <strong>of</strong> knock<br />

holes.<br />

• Do not use multi conductor cable which have more than 5<br />

wires in one core.<br />

Guideline for each installation process 307