5CSL0-06B<br />

2.7.4 Vacuum drying procedure<br />

There are two vacuum drying methods and the appropriate one<br />

should always be chosen to confirm with individual local conditions.<br />

[Normal vacuum drying]........The standard method<br />

[Operational steps]<br />

1. Vacuum drying (1st time): Connect a manifold gauge to the service<br />

port <strong>of</strong> the liquid or gas pipe and operate the vacuum pump<br />

for at least 2 hours.<br />

(The degree <strong>of</strong> vacuum produced should be in excess <strong>of</strong> 5 Torr)<br />

If after 2 hours the vacuum produced has not exceeded 5 Torr<br />

then either there is moisture in the pipe or there is a leak.<br />

Operate the vacuum pump for further one more hour.<br />

If, even after 3 hours, the vacuum has not reached 5 Torr then<br />

check the system for a leak.<br />

2. Carry out vacuum test.<br />

Produce a vacuum in excess <strong>of</strong> 5 Torr and do not release it for<br />

an hour or more. Check the vacuum gauge to make sure that it<br />

has not risen. (If the gauge rise then there is still moisture in the<br />

pipe or there is a leak somewhere.)<br />

3. Additional charge <strong>of</strong> refrigerant.<br />

Connect the charging cylinder to the liquid pipe service port and<br />

charge with the required amount <strong>of</strong> refrigerant.<br />

4. Open stop valve to the full.<br />

Open the stop valve on the liquid and the gas pipes to the full.<br />

NOTE<br />

Vacuums should be produced in both the liquid and the gas pipes.<br />

(Because there are a large number <strong>of</strong> functional components in the<br />

indoor unit which cut <strong>of</strong>f the vacuum mid-way through)<br />

Rising pressure<br />

Falling<br />

pressure<br />

(vacuum)<br />

+0.05MPa<br />

(Atmospheric<br />

pressure)<br />

0 MPa<br />

Vacuum<br />

drying<br />

Vacuum drying works<br />

Maintaining<br />

vacuum test<br />

(2 hours) (1 hours)<br />

Time required: approximately 3 hours.<br />

Guideline for each installation process 315<br />

0 MPa<br />

-200 mmHg<br />

-400 mmHg<br />

-600 mmHg<br />

-700 mmHg<br />

-760 mmHg<br />

-755 mmHg<br />

(5 Torr)<br />

Time.<br />

Additional refrigerant<br />