5CSL0-06B<br />

Models : AUUW186DH + ATNH18GPLED<br />

[UU18WH UED] + [UT18 NPD]<br />

• Cooling Capacity<br />

Model ATNH18GPLED[UT18 NPD]<br />

AFR 17<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.39 5.04 0.98 5.16 4.87 1.03 4.84 4.68 1.38 4.70 4.52 1.54 4.49 4.38 1.69 4.37 4.23 1.66<br />

16.0 22.0 5.72 5.10 1.33 5.49 4.95 1.35 5.17 4.77 1.63 5.02 4.61 1.75 4.82 4.49 1.82 4.69 4.34 1.73<br />

18.0 25.0 6.06 5.15 1.44 5.82 5.00 1.45 5.50 4.83 1.71 5.35 4.69 1.78 5.14 4.57 1.85 5.02 4.42 1.73<br />

19.0 27.0 6.22 5.19 1.46 5.98 5.05 1.47 5.67 4.89 1.73 5.50 4.73 1.78 5.31 4.63 1.85 5.18 4.49 1.73<br />

22.0 30.0 6.72 5.30 1.46 6.48 5.17 1.50 6.16 5.02 1.77 6.00 4.88 1.87 5.80 4.77 1.88 5.67 4.64 1.75<br />

24.0 32.0 7.05 5.40 1.45 6.81 5.27 1.51 6.49 5.13 1.80 6.33 4.99 1.91 6.13 4.90 1.92 6.00 4.76 1.78<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Heating Capacity<br />

Model ATNH18GPLED[UT18 NPD]<br />

AFR 17<br />

Indoor Air<br />

Temperature<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

TC SHC PI<br />

4.24 4.10 1.49<br />

4.57 4.21 1.51<br />

4.90 4.30 1.47<br />

5.06 4.37 1.46<br />

5.55 4.52 1.46<br />

5.88 4.65 1.49<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 4.31 2.03 4.60 2.07 5.13 1.96 5.65 1.83 6.15 1.73 6.55 1.69 6.73 1.60<br />

18 4.26 2.06 4.59 2.12 5.14 2.02 5.64 1.89 6.11 1.77 6.47 1.72 6.70 1.62<br />

20 4.24 2.10 4.59 2.17 5.14 2.08 5.63 1.94 6.05 1.81 6.43 1.75 6.72 1.63<br />

21 4.22 2.12 4.59 2.20 5.14 2.11 5.61 1.96 6.01 1.83 6.43 1.76 6.67 1.63<br />

22 4.22 2.14 4.59 2.23 5.14 2.14 5.60 1.99 5.97 1.84 6.42 1.77 6.62 1.63<br />

24 4.18 2.18 4.54 2.27 5.08 2.17 5.57 2.01 5.96 1.85 6.31 1.77 6.58 1.64<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 203