Clearance space 5CSL0-06B<br />

4.6 Clearance space<br />

4.6.1 Clearance around outdoor unit<br />

AUUW096D [UU09W ULD]<br />

AUUW126D [UU12W ULD]<br />

AUUW186D [UU18W UED]<br />

AUUW186D1[UU18W UED1]<br />

AUUW246D[UU24W UED]<br />

AUUW306D[UU30W UED]<br />

AUUH126D [UU12 ULD]<br />

AUUH186D [UU18 UED]<br />

AUUH246D[UU24 UED]<br />

AUUH306D[UU30 UED]<br />

200 mm or more<br />

300 mm<br />

or more 300 mm<br />

or more<br />

300 mm<br />

or more<br />

200 mm or more<br />

300 mm<br />

or more<br />

200 mm<br />

or more<br />

Fence or<br />

obstacles<br />

Air inlet grille<br />

Sunro<strong>of</strong><br />

100 100 mm<br />

mm<br />

or or more<br />

600 mm or m<br />

(Service spac<br />

More than 50cm<br />

(Service space)<br />

• Ensure that the space around the back is more than 200 mm on the opposite to the PCB side and secure 600 mm<br />

space near the compressor and PCB side <strong>of</strong> the aircondition for service.<br />

AUUW366D[UU36W UED]<br />

AUUW368D[UU37W UED]<br />

AUUH368D[UU37 UED]<br />

AUUW216DH [UU21WH U4D]<br />

AUUW246DH [UU24WH U4D]<br />

• Ensure that the space around the back is<br />

more than 300 mm on the opposite side<br />

to the PCB side and secure 600 mm<br />

space near the compressor and PCB<br />

side <strong>of</strong> the air conditioner for service.<br />

AUUW426D[UU42W U3D]<br />

AUUW486D[UU42W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

AUUH488D[UU48 U3D]<br />

AUUH608D[UU60 U3D]<br />

• Install the unit so that its discharge port faces to the<br />

wall <strong>of</strong> the building.<br />

Keep a distance 500mm or more between the unit<br />

and the wall surface.<br />

• Supposing the wind direction during the operation<br />

season <strong>of</strong> the air conditioner, install the unit so that<br />

the discharge port is set at right angle to the wind<br />

direction.<br />

300 mm<br />

or more<br />

Fence or<br />

obstacles<br />

Sunro<strong>of</strong><br />

Turn the air outlet side toward the<br />

building's wall, fence or windbreak<br />

screen.<br />

300 mm<br />

or more<br />

600 mm or more<br />

(Service space)<br />

More than 50cm<br />

(Service space)<br />

364 Installation <strong>of</strong> outdoor unit<br />

500<br />

Strong<br />

wind<br />

Blown<br />

air<br />

Sunro<strong>of</strong><br />

Strong<br />

wind<br />

Set the otlet side at a rignt angle<br />

to the direction <strong>of</strong> the wind.